Part 6: Common Reference Material
6 - 66
2.3.3 Conversion rules (MR-J3-_B_ and MR-J3W-_B => MR-J4-_B_ and MR-J4W2-_B)
(1) Conversion rules (MR-J3-_B_ (standard) and MR-J3W-_B (standard) => MR-J4-_B_ (standard) and
MR-J4W2-_B (standard))
The following table shows the servo parameter conversion rules from MR-J3-_B_ (standard) and MR-
J3W-_B (standard) to MR-J4- _B_ (standard) and MR-J4W2-_B (standard).
Servo parameters not specified in the following table will be set to the initial values.
POINT
Because the servo parameters of MR-J3-_B_/MR-J3W-_B and those of MR-J4-
_B_/MR-J4W2-_B are not completely interchangeable, the conversion rules may
not be applied. Check the operations and review the settings as necessary.
The parameter writing inhibit after parameter conversion is the initial value (the
following setting value).
• MR-J4-_B_ and MR-J3W-_B: [Pr. PA19 Parameter writing inhibit] = "00ABh"
Various offset parameters cannot be converted. Change the settings as
necessary.
• MR-J4-_B_ and MR-J3W-_B: [Pr. PC11]/[Pr. PC12]
When the geared servo motor is replaced, the reduction ratio may differ before
and after the replacement. Check the specifications of the servo motor and
review the electronic gear settings as necessary. For the electronic gear
settings, refer to the controller instruction manual.
Some parameters are not supported depending on the software version of the
servo amplifier. Refer to section 2.3.4 for details.
Refer to section 2.3.4 (2) for differences between the servo parameters of MR-
J3-_B_ and MR-J3W-_B.
MR-J3-_B_/MR-J3W-_B MR-J4-_B_/MR-J4W2-_B
Conversion rules
No. Name Type
Target
No.
Type
Target
PA02 Regenerative option
Hex
_ _ XX
PA02
Hex
_ _ XX The setting value will be maintained.
PA03 Absolute position detection system
Hex
_ _ _ X
PA03
Hex
_ _ _ X The setting value will be maintained.
PA04 Function selection A-1
Hex
_ X_ _
PA04
Hex
_ X_ _ The setting value will be maintained.
PA08 Auto tuning mode
Hex
_ _ _ X
PA08
Hex
_ _ _ X The setting value will be maintained.
PA09 Auto tuning response
Dec
-
PA09
Dec
-
The value 4 is added to the setting
value.
PA10 In-position
range
Dec
-
PA10 Dec
-
The setting value will increase by 16
times when it is 4095 or smaller.
The setting value other than the above
will be 65535.
PA14 Rotation direction selection
Dec
-
PA14
Dec
-
The setting value will be maintained.
PA15 Encoder output pulses
Dec
-
PA15
Dec
-
When the setting value of PC03 is
_ _ 1_, the setting value of PA15 is
increased by 16 times.
However, when the value is 65535 or
larger, the setting value will be
65535.
When the setting value of PC03 is
other than _ _1_, it will be
maintained.
PB01
Adaptive tuning mode
(Adaptive filter
II
)
Hex
_ _ _ X
PB01
Hex
_ _ _ X The setting value will be maintained.
PB02
Vibration suppression control tuning
mode (advanced vibration
suppression control)
Hex
_ _ _ X
PB02
Hex
_ _ _ X The setting value will be maintained.
Содержание Melservo MR-J3-100B
Страница 17: ...8 MEMO ...
Страница 18: ...Part 1 Summary of MR J3 MR J3W Replacement 1 1 Part 1 Summary of MR J3 MR J3W Replacement ...
Страница 145: ...Part 3 Review on Replacement of MR J3 _B_ with MR J4 _B_ 3 48 MEMO ...
Страница 146: ...Part 4 Replacement of MR J3W _B with MR J4W2 _B 4 1 Part 4 Review on Replacement of MR J3W _B with MR J4W2 _B ...
Страница 195: ...Part 4 Replacement of MR J3W _B with MR J4W2 _B 4 50 MEMO ...
Страница 196: ...Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ 5 1 Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ ...
Страница 277: ...Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ 5 82 MEMO ...
Страница 278: ...Part 6 Common Reference Material 6 1 Part 6 Common Reference Material ...
Страница 418: ...Part 7 Review on Replacement of Motor 7 1 Part 7 Review on Replacement of Motor ...
Страница 564: ...Part 9 Startup Procedure Manual 9 1 Part 9 Startup Procedure Manual ...
Страница 567: ...Part 9 Startup Procedure Manual 9 4 MEMO ...
Страница 589: ...L NA 03127ENG C ...