Table 9: DEOL Loop Status
Loop Resistance
Loop Status
0Ω (shorted wire, loop shorted)
Fault
5600Ω (contact closed)
Secure
Infinite (broken wire, loop open)
Tamper
11200Ω (contact open)
Violated
PGM Wiring
Min/max operating voltages for devices, sensors and modules is 9.5VDC - 14VDC. PGMs switch to
ground when activated from the alarm controller. Connect the positive side of the device to the AUX
+ terminal and the negative side to a PGM terminal. PGM 1, 3, 4 supply up to 50mA; PGM 2 supplies
up to 300mA.
A relay is required for current levels greater than 50mA or 300mA. PGM2 can also be used for 2-wire
smoke detectors, 24-hr burglary input alarm.
Note:
Use SEOL resistors on Fire zones only.
Figure 12: LED Output with Current Limiting Resistor and Optional Relay Driver Output.
Bell Wiring
These terminals supply 700mA of current at 10.4 - 12.5VDC for commercial/ residential installations.
To comply with NFPA 72 Temporal Three Pattern requirements, section [013] Opt [8] must be ON.
Note that steady, pulsed alarms are also supported.
Figure 13: Bell Wiring
The Bell output is supervised and power limited by 2A thermistor. If unused, connect a 1000 Ω
resistor across Bell+ and Bell- to prevent the panel from displaying a trouble.
.
Telephone Line Wiring
Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an RJ-31x connector as indicated
in the following diagram. For connection of multiple devices to the telephone line, wire in the
sequence indicated. Use 26 AWG wire minimum for wiring.
33
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual