Note:
If the Auto-arm toggle option is disabled, the Auto-arm Pre-alert still occurs when a
time is programmed for that day (if enabled) and the event is logged and communicated. This
option does not directly affect the functionality of Auto-arm. If Late to Close is enabled and
Auto-arming is not, LCD keypads display “System Arming in Progress” during the Late to Close
Pre-alert.
6 - Daylight Savings Time
ON: The alarm system adjusts between Daylight and Standard times according to the times
programmed in System Timers ([005] options 001-002).
Note:
Auto-arm and Test Transmissions should not be attempted between 0200 and 0300
hours, as they will be missed during a daylight savings clock adjust. Events programmed to
occur between 0100 and 0200 will occur twice during a daylight savings clock adjust. Daylight
Savings Time programming should not conflict with the Auto-arm and Test Transmissions
programming.
OFF: The alarm system makes no automatic time adjustments for Daylight Saving time.
7 - Silence Chime During Quick Exit Delay
ON: Door chime does not sound during quick exit.
OFF: Door chime sounds during quick exit, according to zone settings.
8 - Bell Squawk on Away Arm/ Disarm Only
ON: Bell Squawks are only heard when away arming, as well as when disarming from Away mode.
This feature prevents the siren from activating when arming in stay and night modes.
OFF: Bell Squawks are heard during all types of arming and disarming.
Note:
This option follows the “Bell Squawk Attribute” features if they are enabled.
[018] System Option 6
1 - Test Transmission Exception
ON: The alarm system does not send a test transmission if a transmission was sent to the receiver
within the programmed interval as set in section [377]>
[003] – Periodic Test Transmission Cycle
.
OFF: Test transmissions are always sent at the programmed interval.
2 - Real-Time Bypass Reporting
ON: When a non-24-hour zone is bypassed in [*][1], the system immediately logs and
communicates the bypass status of the zone.
Global Zones: 24-hour and non-24 hour zone bypasses are logged and communicated in real time.
Non-24 hour zone unbypass events are generated when the last assigned partition is disarmed.
OFF: When a non 24-hour zone is bypassed in [*][1], the system logs and communicates the bypass
status of the zone only after the partition is armed. This option is applied regardless of how zones
are bypassed in [*][1], recall bypass group, clear all bypasses, bypass open zones, bypass recall as
well as other methods such as bypassing via ITv2 or DLS.
Global Zones: 24-hour zone bypasses are logged and communicated in real time. Non 24-hour zone
bypass events are logged and communicated when armed. Non 24-hour zone unbypass events are
logged and communicated when the last partition is disarmed.
3 - Armed Status PGM ON at End of Exit Delay
ON: PGMs are activated at the end of exit delay. This applies to PGMs with one of the following
armed status attributes:
• System Armed Status PGM
117
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual