OFF: Siren output pulses when in alarm.
–
Door Chime
ON: The keypad chimes when the zone is open and when the zone is secured.
OFF: The zone does not chime.
–
Bypass Enabled
ON: The zone can be manually bypassed.
OFF: The zone cannot be bypassed.
Note:
Bypass shall not be enabled for fire zones.
–
Force Arm
ON: The system can be armed with the zone open. The zone is temporarily bypassed and, when
secured, is monitored by the system.
Note:
When open zones cancel arming is enabled [021][7], the system can begin arming with
an open, force armable zone, but if the zone is still open when the exit delay timer expires, the
arming will be cancelled.
OFF: The system cannot be armed if the zone is open.
–
Swinger Shut Down
ON: When the zone goes into alarm for the number of times programmed in the Swinger Shutdown
), it shuts down with no further transmissions sent to the
monitoring station. The siren follows swinger shutdown if programmed.
OFF: Swinger shutdown is disabled. All alarms are transmitted.
–
Transmission Delay
ON: Reporting of zone alarms is delayed for the programmed time in section 377 (
). If a valid access code is entered within this time, no alarm signal is
communicated.
OFF: When an alarm occurs, the reporting code is transmitted immediately.
Burglary verification
The PowerSeries Neo system includes cross zone and sequential detection features that require
an activation on two or more zones, within a given time period, to generate a confirmed alarm and
immediate police response.
Note:
This feature must be enabled and configured by your installer.
–
Normally Closed (NC)
ON: The zone requires a normally closed loop.
OFF: The zone follows programming in section [013] option 2.
See note after option 11.
–
Single End of Line (SEOL) Resistors
ON: The zone requires a single end-of-line resistor (5.6K).
OFF: The zone follows programming in section [013] option 2.
See note after option 11.
–
Double End of Line (DEOL)
ON: The zone requires two end-of-line resistors (5.6K).
OFF: The zone follows programming in section [013] option 2.
89
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual