
Enable DLS/Allow System Service
Menu: [*][6][Master Code] > System Serv/DLS
Keypad: [*][6][Master Code] + 05
This function enables and disables the DLS window for either 1 or 6 hours depending on the
programming of section [025] option [7].
This function also enables the end user to provide or deny access to [*][8] Installer Programming.
When enabled, the installer can access Installer Programming either by DLS or via [*8] if a pre-
programmed window has been set. After the window has expired, Installer Programming is
unavailable again until the window is re-opened.
Note:
DLS programming is not UL tested.
Other programming options that may affect this function:
User Call-up
Menu: [*][6][Master Code] ; User Call-up
Keypad: [*][6][Master Code] + 06
When selected, this function makes a single attempt to call the downloading computer. The
downloading computer must be waiting for the call before downloading can be performed. Only
one call-up is attempted. If a DLS phone number is not programmed, the alarm panel attempts to
reach the DLS computer via IP connection. If the communicator is not properly configured for IP, an
error tone is sounded.
User Walk Test
Menu: [*][6][access code] > Walk Test
Keypad: [*][6][access code] + 08
Selecting this function places the alarm panel into user walk test mode. The Ready, Armed and
Trouble LEDs on the keypad flash to indicate that the test is active. If zones are tripped during a
walk test, the system sounds a steady 2-second tone on all keypads to indicate that the zone is
working correctly.
The walk test can be stopped at any time by re-entering [*][6][Master Code][08] on the keypad. The
test automatically terminates after 15 minutes of inactivity. An audible warning begins 5 minutes
prior to automatic termination.
Note:
Fire and CO alarms are not tested in user's walk test. If a fire or CO alarm is detected,
walk test ends automatically and the appropriate reporting codes are sent immediately to
the monitoring station. Refer to the manufacturers instructions provided with CO and Fire
detectors for testing. This feature is not available in CP-01 systems.
Late to Open
Menu: [*][6][Master Code] > Late To Open
Keypad: [*][6][Master Code] + 09
This function enables or disables the Late to Open option. This option sends a reporting code to the
central monitoring station if the partition has not been disarmed by a programmed time.
Other programming options that may affect this function:
[211] Miscellaneous Open/Close Events
.
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual
68