currently active alarms) when the TLM fault occurs. The alarms in memory must have exceeded the
bell timeout.
147 - Kissoff
This PGM output activates for two seconds after the alarm system receives a kissoff signal from the
central station.
148 - Ground Start
This output activates for two seconds before the alarm system attempts dialing to obtain a dial tone
on Ground Start telephone equipment. Two 2-second pauses must be inserted at the beginning of
the telephone number when using this option.
149 - Alternate Communicator
This output can be used to trigger inputs on a third-party communicator for the purpose of
triggering alarm communications to a monitoring station. This output can be programmed to
activate when any of the following system events (alarms) occur on the system:
• Fire (Fire Key, Fire Zones)
• Panic (Panic Key and Panic Zones)
• Burglary (Delay, Instant, Interior, Stay/Away and 24-hour Burglary Zones)
• Opening/Closing Events
• Zone Auto-Bypass. (Please
for details).
• Medical (Medical Key, Medical and Emergency Zones)
• Burglary Verified
• Opening After Alarm
• Emergency Alarm
• Duress Alarm
• Holdup Verified
In the armed state, this output deactivates when the system is disarmed. If an alarm activates this
output in the disarmed state, the output deactivates if a valid access code is entered within the bell
timeout or if the system is armed after the bell timeout has expired.
This output activates for silent and audible alarms or medical conditions only. It will not activate
during pre-alert or delays.
Note:
The PGM attributes for this option, programmed in section [010], differ from the
standard selection of attributes normally programmed.
Note:
When this PGM is configured to provide Opening/Closing status, the PGM must be
programmed as a timed output, not latching.
155 - System Trouble
This output can be programmed to activate when any of the following trouble conditions are
present:
• Service Required
• Loss of Clock
• DC Trouble
• Bus Voltage
97
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual