A minimum of two receivers should be enabled for this feature to operate as intended. This feature
should not be enabled unless the panel is programmed to use backup communication paths.
OFF: If a TLM trouble is present, the number of dialing attempts programmed shall be attempted
before moving on to the backup receiver.
8 - Activity Delinquency
ON: Inactivity on a partition for a programmed duration (section [377] option 002, Delinquency
Transmission Delay) transmits a Delinquency code to the central station. This option is designed to
help monitor the elderly or disabled. The counter is reset if zone activity is detected or if the system
is armed. The Delinquency Transmission Delay is in hours.
Note:
Delinquency code is not transmitted while Away armed. Activity on bypassed zones does
not affect this timer.
OFF: The Delinquency reporting code is sent when the programmed number of days for
delinquency (section [377]) expires without the partition being Armed. Once the code is sent, the
timer is not started again until the partition has been armed. Each day programmed in the counter
represents one day plus the time it takes for the partition to reach midnight. To disable this feature,
program 000 in section [377]>[002] option 5.
[381] Communicator Option 2
1 - Keypad Ringback
ON: When the Opening After Alarm reporting code is successfully transmitted to a programmed
telephone number, the keypad emits a series of 8 beeps to confirm to the occupant that the code
was sent and received. Ringback occurs for each successfully reported Opening After Alarm code.
OFF: When the Opening After Alarm reporting code is successfully transmitted to a programmed
telephone number, the keypad does not sound ringback.
2 - Bell Ringback
ON: When the Opening After Alarm reporting code is successfully transmitted to a programmed
telephone number, the siren emits a series of 8 squawks to confirm to the occupant that the code
was sent and received. Ringback occurs for each successfully reported Opening After Alarm code.
OFF: When the Opening After Alarm reporting code is successfully transmitted to a programmed
telephone number, the siren does not sound ringback.
4 - Closing Confirmation Enabled/Disabled
ON: When a Closing reporting code is successfully transmitted to a programmed telephone
number, the keypad emits a series of 8 beeps to confirm to the occupant that the Closing Code was
sent and received.
OFF: No keypad ringback is generated when a Closing reporting code is successfully transmitted.
8 - Communications Priority Enabled/Disabled
About this task:
ON: Events follow the priority level indicated in ULC-S559 standard.
Concurrent event communications are prioritized in the following order (highest to lowest priority):
1. Fire Alarms
2. CO Alarm
3. Fire Supervisories
4. Fire Trouble
5. Monitoring (Medical, Panic or Security)
6. All others such as restorals for fire alarms, supervisories, troubles and monitoring.
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual
144