4 - User Call-Up
ON : A single call attempt can be made to the downloading computer using [*][6][Master Code]
[06].
OFF: [*][6][Master Code][06] does not allow initiation of a downloading session.
6 - Panel Call-Up and Baud Rate
ON : When a DLS/SA session is initiated by the user, the initial header is sent at 300 baud.
OFF: When a DLS/SA session is initiated by the user, the initial header is sent at 110 baud. The alarm
system will then switch to 300 baud in order to receive the response from the DLS computer.
7 - Alternate Communicator DLS
ON: When this feature is enabled, the alarm system responds to DLS requests through the
alternate communicator IP or cellular paths at any time, regardless of whether the DLS window is
active or not.
However, if a pre-defined number of consecutive incorrect DLS access codes is detected (
) while trying to establish a connection, alternate communicator DLS access is locked
out until the next hour roll-over.
OFF: When this feature is disabled, the alarm system only responds to DLS requests through the
alternate communicator IP or cellular paths when the DLS window is active.
The DLS/SA window is active following a power up or if enabled using [*][6][maser code][05]
(System Service/DLS).
Note:
This option controls DLS over alternate communicator only.
[402] PSTN DLS Phone Number Programming
This section is used to program the telephone number for DLS downloading over PSTN. This
phone number is used for User Call Up, Periodic DLS and DLS Call back. If no phone number is
programmed, the system attempts to use the alternate communicator IP path (if configured).
The maximum number length is 32 digits.
[403] DLS Access Code
This 6-digit hexadecimal code allows the alarm system to confirm the identity of the downloading
computer.
If the code does not match the computer, the alarm system does not allow DLS access.
Once a DLS connection is established, the operator is allowed three attempts to enter the correct
access code. If these attempts are unsuccessful, the alarm system disconnects and a new attempt
must be made.
If cellular or IP paths are used for the DLS connection, a pre-programmed number of unsuccessful
attempts causes a 1-hour DLS lockout. Number of attempts is programmed in section [012].
[404] DLS/SA Panel ID
This 10-digit hexadecimal code identifies the alarm system to the downloading computer.
[405] PSTN Double Call Timer
Use this section to program the amount of time that can elapse between the first and second call
when using Double Call downloading. Valid entries are 001 to 255 (seconds).
[406] PSTN Number of Rings to Answer On
The value in this section determines how many rings are required in order to establish a DLS
connection. Default value is 000 rings. Valid entries are [000]-[020].
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual
148