Proximity Tag Used
This option is used to define which proximity tag will activate PGM outputs programmed as [165]
Prox Used. Enter 000 to enable this PGM attribute for all user proximity tags, or enter user number
0002-1000 to have this attribute activated by a specific user proximity tag.
Command Output 1-4
This option is used to assign a schedule, programmed in section [601]-[604], for the command
output PGMs to follow. Program 001-004 to for schedules 1-4. Program 000 to activate the PGM
when a proximity tag is presented.
[012] System Lockout
Keypad Lockout – Number of Invalid Local Attempts
This option controls the number of invalid access code entries allowed before the keypad is locked.
When keypad lockout occurs, the system is inaccessible by keypad for the programmed duration. If
the number of invalid attempts is not reached within one hour, or if a valid access code is entered,
the counter is reset to 0. Valid entries are 000 to 255 minutes. Entering 000 disables the feature.
Presenting an invalid tag counts toward keypad lockout.
Note:
For EN 50131 certified installations, maximum number of attempts is 10.
Keypad Lockout Duration
This programming option determines the length of time the keypad is locked out for. If the system
cold starts while in keypad lockout, the lockout is removed. Valid entries are 000 to 255 minutes.
Entering 000 disables keypad lockout.
Note:
For EN 50131 certified installations, minimum of duration is 2 minutes.
Remote Lockout DLS
This programming option determines the number of invalid access code entries allowed via SMS or
DLS before remote access is locked out for the programmed duration (see below). If the number of
invalid attempts is not reached within one hour, or if a valid access code is entered through SMS or
DLS, the counter is reset to 0. The valid entries are 003 to 255 attempts. Default is 6 attempts. The
number of invalid attempts is fixed at 5 when using System Administrator Software and the lockout
duration is 1 hour.
Note:
DLS tries to connect using the programmed DLS Access code first and, if
unsuccessful, using the default DLS access code. Two failed attempts are counted if both codes
are incorrect.
Remote Lockout Duration
This programming option determines how long the remote lockout lasts. If the system cold starts
while in remote lockout, the lockout restarts for the programmed duration. Valid entries are 001 to
255 minutes. Entering 000 disables remote lockout.
System Options
[013] System Option 1
1 - NC Loop/EOL
ON: All zones are wired as normally closed circuits with returns connected to a COM terminal. The
end-of-line resistor is not required. An alarm is generated when the circuit is opened.
111
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference