• AMTB Control Panels, SIA False Alarm Reduction
The product is labeled with the UL and ULC listing marks along with the SIA CP-01 compliance
statement (Also Classified in accordance with SIA-CP-01 Standard) as proof of compliance with the
above mentioned standards. For further information on this product’s listings please also refer
to the official listing guides published at the UL web site (www.ul.com) under Online Directions
Section.
UL/ULC Residential Fire and Burglary Installations:
For ULC Installations refer to the Standard for the Installation of Residential Fire Warning Systems,
CAN/ULC-S540.
• All burglary-type zones shall be configured with SEOL or DEOL configuration. Use model
EOLR-2 (refer to section [002], bit 10 or 11 shall be ON)
• Use at least one PG9936/PG9926/PG9916 Smoke Detector for Fire Installations (section [001],
fire zone shall be programmed as type 025)
• The entry delay shall not exceed 45 seconds (see section [005])
• The exit delay shall not exceed 60 seconds (refer to section [005])
• The minimum Bell Time-out is 4 minutes (refer to section [005])
Note:
For UL Commercial Burglary installations, minimum bell time-out is 15 min.
• Temporal Three Fire Signal shall be enabled (section [013], option 8 ON)
• Arm/Disarm Bell Squawk shall be enabled when using wireless key PG4939/PG4929/PG4949
(section [014], option 1 shall be ON)
• A code shall be required for bypassing (section [023], option 4 shall be ON)
• Trouble beeps shall be enabled (section [022], option 7 shall be ON)
• For fire and CO applications, RM-1(C) or RM-2 power loop supervision relay shall be connected
to Aux power output to report wiring faults if it is used for powering fire and CO detection
devices. For wiring, see manual p/n: 29009812.
• AC trouble indication LED shall be enabled (Keypad Programming, section [022], options 5 and
6 shall be ON)
• DACT Communicator shall be enabled for Supervising Station Monitoring (section [380], option
1 shall be ON)
• For UL Residential Fire and burglary installations, a code shall be required to view the [*][2]
trouble menu (Section [023], option 5 shall be ON)
• A test transmission shall be sent to the monitoring station every 7 days (Section [377][003]
shall be set to 007; 007 is the default setting)
• For UL residential fire applications at least one LCD keypad (model HS2LCD(P), HS2LCDRF(P)9)
or touchscreen keypad (Model HS2TCHP) shall be used.
• For UL Residential Fire and burglary installations, 2 UL listed compatible keypads (e.g.
HS2LCD(P), HS2LCDRFP9, HS2TCHP) shall be used, each having communication bus wiring
directly connected to the RED/BLK/YEL/GRN, located on the main control panel board
assembly.