Figure 2: Wiring Routing (EN50131 only)
Corbus Wiring
The RED and BLK Corbus terminals are used to provide power while YEL and GRN are used for data
communications. The 4 Corbus terminals of the alarm controller must be connected to the 4 Corbus
terminals or wires of each module.
The following conditions apply:
• Corbus should be run with minimum 22 gauge quad, two pair twisted preferred.
• The modules can be home run to the panel, connected in series or can be T-tapped.
• Do not use shielded wire for Corbus wiring.
Note:
Any module can be connected anywhere along the Corbus. Separate wire runs for
keypads, zone expanders etc. are not necessary.
Note:
No module can be more than 1,000'/305m (in wire length) from the panel. Do not use
shielded wire for Corbus wiring.