Wiring
All wiring entry points on the enclosure are designated by arrows. All circuits are classified UL
power limited except for the battery leads. Minimum 1/4” (6.4mm) separation must be maintained
at all points between power limited and non-power limited wiring and connections.
Terminal Descriptions
The following terminals are available on the PowerSeries Neo alarm controller.
Terminal
Description
BAT+, BAT-
Battery terminals. Use to provide backup power and additional current when system
demands exceed the power output of the transformer, such as when the system is in
alarm. Note: Do not connect the battery until all other wiring is complete.
AC
Power terminals. Connect the battery before connecting the AC. Do not connect the
battery or transformer until all other wiring is complete.
AUX+, AUX-
Auxiliary terminals. Use to power modules, detectors, relays, LEDs, etc. (700mA MAX).
Connect the positive side of device to AUX+, the negative side to AUX-.
BELL+, BELL-
Bell/Siren power (700mA MAX). Connect the positive side of any alarm warning device to
BELL+, the negative side to BELL-.
RED, BLK, YEL, GRN
Corbus terminals. Use to provide communication between the alarm controller and
connected modules. Each module has four Corbus terminals that must be connected to
the Corbus.
PGM1 to PGM4
Programmable output terminals. Use to activate devices such as LEDs.
(PGM1, PGM3, and PGM4: 50mA PGM2: 300mA or can be configured as an input)
Z1 to Z8
COM
Zone input terminals. Each zone should have one detection device; however, multiple
detection devices can be wired to the same zone.
EGND
Earth ground connection.
TIP, RING, T-1, R-1
Telephone line terminals.
PCLINK_1
DLS/SA
PCLINK_2
DLS/SA, Alternate Communicator
Wire Routing for Power & Non-Power Limited
All wiring entry points are designated on the diagram by arrows. All circuits are classified UL
installation power limited except for the battery leads which are not power limited.
A minimum ¼” (6.4mm) separation must be maintained at all points between power limited and
non-power limited wiring and connections. See
Note:
Wire entry for power limited wiring must be separated by a different entry access from
non-power limited wiring.
Figure 1: Wiring Routing (North America only)
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual