Remote Access/SMS
-
Do Not Use
DLS Arm
N
Away
NAA Arming
N
Away
Do not use exit delay termination with this zone type. Away arming with this zone bypassed
prevents arming.
[002] Zone Attributes
Zone attributes are used to customize the operation of zones. When a zone type (section [001]) is
programmed, the default zone attribute is automatically assigned.
When programming attributes using LED/ICON keypads:
• Ready light ON: Program attributes [1-8]
• Ready light and Armed light ON: Program attribute [9-16] (press [1] for option 9, press [6] for
option 14 etc.)
• Press [9] to switch between attributes [1-8] and attributes [9-16].
Note:
These attributes override default settings. Do NOT change fire zone attributes from their
default settings.
[001]-[128] Select Zone
The attributes listed below can be enabled and disabled for each zone.
Assign zone attributes:
[002]>[001]-[128]>Select one of the following zone attributes:
1 – Bell Audible
2 – Bell Steady
3 – Chime Function
4 – Bypass Enabled
5 – Force Arm
6 – Swinger Shutdown
7 – Transmission Delay
8 – Burglary Verification
9 – Normally Closed
10 – Single EOL
11 – Double EOL
12 – Fast/Normal Loop Response
13 – Zone 2-way Audio Activation
14 – Hold Up Verification
–
Bell Audible
ON: An alarm activates the siren.
OFF: Silent alarm.
–
Bell Steady
ON: Siren output is steady when in alarm.
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual
88