B
8
Message Configuration: Response
Transmission time required:
A time period between reception of a query from the master and transmission of a
response from the inverter is the sum of the silent interval (3.5 characters long) +
C078 (transmission latency time).
The master must provide a time period of the silent interval (3.5 characters long or
longer) before sending another query to an inverter after receiving a response from
the inverter.
Normal response:
When receiving a query that contains a function code of Loopback (08h), the inverter
returns a response of the same content of the query.
When receiving a query that contains a function code of Write in Register or Coil
(05h, 06h, 0Fh, or 10h), the inverter directly returns the query as a response.
When receiving a query that contains a function code of Read Register or Coil (01h
or 03h), the inverter returns, as a response, the read data together with the same
slave address and function code as those of the query.
Response when an error occurs:
When finding any error in a query (except for a transmission error), the inverter
returns an exception response without executing anything.
You can check the error by the function code in the response. The function code of
the exception response is the sum of the function code of the query and 80h.
The content of the error is known from the exception code.
Field Configuration
Slave address
Function code
Exception code
CRC-16
Exception
Code
Description
0 1 h
The specified function is not supported.
0 2 h
The specified function is not found.
0 3 h
The format of the specified data is not acceptable.
2 1 h
The data to be written in a holding register is outside the inverter.
2 2 h
The specified functions are not available to the inverter.
Function to change the content of a register that cannot be changed while
the inverter is in service
Function to submit an ENTER command during running (UV)
Function to write in a register during tripping (UV)
Function to change the I/O terminal configuration which is not allowed.
Function to change active state of RS (reset) terminal
Function to write in a register during auto-tuning
Function to write in a register locked by password
2 3h
The register (or coil) to be written in is read-only
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...