C
−
−
−
−
14
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
A B Initial data Units
b010
Number of retry on over
voltage / over current trip
Range is 1 to 3 times
3
times
b011
Retry wait time on over
voltage / over current trip
Range is 0.3 to 100 sec.
1.0
sec
B012
Level of electronic thermal
Set a level between 20% and 100%
for the rated inverter current.
Rated
current
for each
inverter
model *1
A
B212
Level of electronic thermal,
2
nd
motor
A
B013
Electronic thermal
characteristic
Select from three curves, option
codes:
00
…
Reduced torque
01
…
Constant torque
02
…
Free setting
01
−
B213
Electronic thermal
characteristic, 2
nd
motor
01
−
b015
Free setting electronic
thermal ~freq.1
Range is 0 to 400Hz
0.0
Hz
b016
Free setting electronic
thermal ~current1
Range is 0 to inverter rated
current Amps
0.00
Amps
b017
Free setting electronic
thermal ~freq.2
Range is 0 to 400Hz
0.0
Hz
b018
Free setting electronic
thermal ~current2
Range is 0 to inverter rated
current Amps
0.00
Amps
b019
Free setting electronic
thermal ~freq.3
Range is 0 to 400Hz
0.0
Hz
b020
Free setting electronic
thermal ~current3
Range is 0 to inverter rated
current Amps
0.00
Amps
B021
Overload restriction
operation mode
Select the operation mode during
overload conditions, four options,
option codes:
00
…
Disabled
01
…
Enabled for acceleration and
constant speed
02
…
Enabled for constant speed
only
03
…
Enabled for acceleration and
constant speed, increase speed
at regen.
01
−
B221
Overload restriction
operation mode, 2
nd
motor
01
−
B022
Overload restriction level
Sets the level of overload
restriction, between 20% and 200%
of the rated current of the inverter,
setting resolution is 1% of rated
current
Rated
current
x 1.5
Amps
B222
Overload restriction level,
2
nd
motor
Rated
current
x 1.5
Amps
B023
Deceleration rate at overload
restriction
Sets the deceleration rate when
inverter detects overload, range is
0.1 to 3000.0, resolution 0.1
1.0
sec.
B223
Deceleration rate at overload
restriction, 2
nd
motor
1.0
sec.
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...