B
39
Register
No.
Function name
Function
code
R/W
Monitoring and setting items
Data
resolution
1375h to
137Ah
(Reserved)
-
-
-
-
137Bh
Brake Control Enable
b120
R/W
0 (disabling), 1 (enabling)
-
137Ch
Brake Wait Time for Release
b121
R/W
0 to 500
0.01
[sec.]
137Dh
Brake Wait Time for Acceleration
b122
R/W
0 to 500
0.01
[sec.]
137Eh
Brake Wait Time for Stopping
b123
R/W
0 to 500
0.01
[sec.]
137Fh
Brake Wait Time for Confirmation
b124
R/W
0 to 500
0.01
[sec.]
1380h
Brake Release Frequency
b125
R/W
0 to 40000
0.01 [Hz]
1381h
Brake Release Current
b126
R/W
0 to 2000
0.1 [%]
1382h
Braking frequency
b127
R/W
0 to 40000
0.01 [Hz]
1383h
(Reserved)
-
-
-
-
1384h
(Reserved)
-
-
-
-
1385h
Deceleration overvoltage
suppression enable
b130
R/W
0 (disabling), 1 (enabling), 2 (enabling with
acceleration)
-
1386h
Decel. overvolt. suppress level
b131
R/W
200 V class: 330 to 390 (V)
400 V class: 660 to 780 (V)
1 [V]
1387h
Decel. overvolt. suppress const.
b132
R/W
10 to 3000
0.01
[sec.]
1388h
Decel. overvolt. suppress
propotional gain
b133
R/W
0 to 500
0.01
1389h
Decel. overvolt. suppress Integral
time
b134
R/W
0 to 1500
0.1 [sec.]
138Ah to
1393h
(Reserved)
-
-
-
-
1394h
GS input mode
b145
R/W
0(non Trip) /1(Trip)
-
1395h
~
1399h
(Reserved)
-
-
-
-
139Ah
Display ex.operator connected
b150
R/W
001 to 060
-
139Bh
~
13A2h
(Reserved)
-
-
-
-
13A3h
1st parameter of Dual
Monitor
b160
R/W
001 to 030
-
13A4h
2nd parameter of Dual
Monitor
b161
R/W
001 to 030
-
13A5h
(Reserved)
-
-
-
-
13A6h
Freq. set in monitoring
b163
R/W
0 (disabling), 1 (enabling),
-
13A7h
Automatic return to the initial
display
b164
R/W
0 (disabling), 1 (enabling),
-
13A8h
Ex. operator com. loss action
b165
R/W
0 (tripping), 1 (tripping after decelerating and
stopping the motor), 2 (ignoring errors),
3 (stopping the motor after free-running),
4 (decelerating and stopping the motor)
-
13A9h
~
13ADh
(Reserved)
-
-
-
-
13AEh
Inverter mode selection
b171
R/W
0 (disabling), 1 (IM mode), 3 (PM motor
mode)
-
13AFh
~
13B6h
(Reserved)
-
-
-
-
13B7h
Initialization trigger
b180
R/W
0 (disabling), 1 (enabling),
-
13B8h
~
1400h
unused
-
-
Inaccessible
-
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...