In standard operation, the inverter uses a reference source selected by parameter
for the output frequency, which may be a fixed value (
), a variable set by the front
panel potentiometer, or value from an analog input (voltage or current). To enable PID
operation, set
=
. This causes the inverter to calculate
the target freq, or setpoint.
A calculated target frequency can have a lot of advantages. It lets the inverter adjust
the motor speed to optimize some other process of interest, potentially saving energy as
well. Refer to the figure below. The motor acts upon the external process. To control that
external process, the inverter must monitor the process variable. This requires wiring a
sensor to either the analog input terminal [O] (voltage) or terminal [OI] (current).
When enabled, the PID loop calculates the ideal output frequency to minimize the loop
error. This means we no longer command the inverter to run at a particular frequency,
but we specify the ideal value for the process variable. That ideal value is called the
setpoint, and is specified in the units of the external process variable. For a pump
application it may be gallons/minute, or it could be air velocity or temperature for an
HVAC unit. Parameter
is a scale factor that relates the external process variable
units to motor frequency. The figure below is a more detailed diagram of the function.
Setpoint
SP
+
PID
Calculation
Error
Freq.
Inverter
Motor
External
Process
Sensor
Process Variable (PV)
PV
Standard setting
Multi-speed
setting
to
POT meter on
ext. panel
1
Setpoint
(Target)
Scale factor
Reciprocal
Frequency
source select
+
P gain
I gain
D gain
+
Frequency
setting
Scale factor
SP
V/I select
[AT]
[L]
A GND
[O]
Voltage
[OI]
Current
PID V/I input select
Process variable (Feedback)
Analog input scaling (OI)
Scale factor
Monitor
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...