Input Function Summary Table
–
This table shows all thirty-one intelligent input
functions at a glance. Detailed description of these functions, related parameters and
settings, and example wiring diagrams are in “Using Intelligent Input Terminals” on
page 4-12.
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
FW
FORWARD Run/Stop
ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Stop Mode, motor stops
RV
Reverse Run/Stop
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
CF1 *1
Multi-speed Select,
Bit 0 (LSB)
ON
Binary encoded speed select, Bit 0, logical 1
OFF
Binary encoded speed select, Bit 0, logical 0
CF2
Multi-speed Select,
Bit 1
ON
Binary encoded speed select, Bit 1, logical 1
OFF
Binary encoded speed select, Bit 1, logical 0
CF3
Multi-speed Select,
Bit 2
ON
Binary encoded speed select, Bit 2, logical 1
OFF
Binary encoded speed select, Bit 2, logical 0
CF4
Multi-speed Select,
Bit 3 (MSB)
ON
Binary encoded speed select, Bit 3, logical 1
OFF
Binary encoded speed select, Bit 3, logical 0
JG
Jogging
ON
Inverter is in Run Mode, output to motor runs at jog
parameter frequency
OFF
Inverter is in Stop Mode
DB
External DC braking
ON
DC braking will be applied during deceleration
OFF
DC braking will not be applied
SET
Set (select) 2nd Motor
Data
ON
The inverter uses 2nd motor parameters for
generating frequency output to motor
OFF
The inverter uses 1st (main) motor parameters for
generating frequency output to motor
2CH
2-stage Acceleration
and Deceleration
ON
Frequency output uses 2nd-stage acceleration and
deceleration values
OFF
Frequency output uses standard acceleration and
deceleration values
FRS
Free-run Stop
ON
Causes output to turn OFF, allowing motor to free
run (coast) to stop
OFF
Output
operates
normally,
so
controlled
deceleration stop motor
EXT
External Trip
ON
When assigned input transitions OFF to ON,
inverter latches trip event and displays
OFF
No trip event for ON to OFF, any recorded trip
events remain in history until reset
USP
Unattended Start
Protection
ON
On powerup, the inverter will not resume a Run
command (mostly used in the US)
OFF
On powerup, the inverter will resume a Run
command that was active before power loss
CS
Commercial
power
source switchover
ON
Motor can be driven by commercial power
OFF
Motor is driven via the inverter
SFT
Software Lock
ON
The keypad and remote programming devices are
prevented from changing parameters
OFF
The parameters may be edited and stored
AT
Analog Input
Voltage/Current Select
ON
Refer to
“Analog Input Settings” on page 3-13.
OFF
RS
Reset Inverter
ON
The trip condition is reset, the motor output is
turned OFF, and powerup reset is asserted
OFF
Normal power-ON operation
PTC
PTC thermistor Thermal
Protection
(C005 only)
ANLG
When a thermistor is connected to terminal [5] and
[L], the inverter checks for over-temperature and
will cause trip event and turn OFF output to motor
OPEN
A disconnect of the thermistor causes a trip event,
and the inverter turns OFF the motor
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...