Second Acceleration and Deceleration Functions
The WJ200 inverter features two-stage acceleration and deceleration ramps. This gives
flexibility in the profile shape. You can specify the frequency transition point, the point
at which the standard acceleration (
) or deceleration (
) changes to the second
acceleration (
) or deceleration (
). Or, you can use intelligent input [2CH] to
trigger this transition. These profile options are also available for the second motor
settings. Select a transition method via
as depicted below. Be careful not to confuse
the
second acceleration/deceleration settings
with settings for the
second motor
!
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
Acceleration time (2)
Duration of 2
nd
segment of
acceleration, range is:
0.01 to 3600 sec.
10.00
sec
Acceleration time (2),
2
nd
motor
10.00
sec
Deceleration time (2)
Duration of 2
nd
segment of
deceleration, range is:
0.01 to 3600 sec.
10.00
sec
Deceleration time (2),
2
nd
motor
10.00
sec
Select method to switch to
Acc2/Dec2 profile
Three options for switching
from 1st to 2nd accel/decel:
2CH input from terminal
Transition frequency
Forward and reverse
00
Select method to switch to
Acc2/Dec2 profile, 2
nd
motor
00
Acc1 to Acc2 frequency
transition point
Output frequency at which
Accel1 switches to Accel2,
range is 0.0 to 400.0 Hz
0.0
Hz
Acc1 to Acc2 frequency
transition point, 2
nd
motor
0.0
Hz
Dec1 to Dec2 frequency
transition point
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 400.0 Hz
0.0
Hz
Dec1 to Dec2 frequency
transition point, 2
nd
motor
0.0
Hz
NOTE: For
and
(and for 2nd motor settings), if you set a very rapid Acc1 or
Dec1 time (less than 1.0 second), the inverter may not be able to change rates to Acc2 or
Dec2 before reaching the target frequency. In that case, the inverter decreases the rate
of Acc1 or Dec1 in order to achieve the second ramp to the target frequency.
=
Transition via 2CH input
Output
frequency
Accel 1
Accel 2
2CH
input
1
0
t
t
0
=
Transition via freq. level
Output
frequency
Accel 1
Accel 2
t
0
Frequency
transition point
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...