3
55
Run/power ON warning time
Inverter outputs the operation time over (RNT) or the plug-in time over (ONT) signal
when the time specified as the run/power ON warning time (
) is exceeded.
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data Units
Run/power ON warning
time
Range is,
.:Warning disabled
. to
.:
10~99,990 hrs (unit: 10)
to
:
100,000~655,350 hrs (unit: 100)
0.
Hrs.
(1)
Operation time over (RNT) signal
To use this signal function, assign function “11 (RNT)” to one of the intelligent
output terminals [11] to [12] (
to
), or to the alarm relay output (
).
Specify the run/power-ON warning time (
).
(2)
Plug-in time over (ONT) signal
To use this signal function, assign function “12 (ONT)” to one of the intelligent
output terminals [11] to [12] (
to
), or to the alarm relay output (
).
Specify the run/power-ON warning time (
).
Rotation restriction related parameters
Rotation direction restriction:
–
The rotation direction restriction function allows
you to restrict the direction of the motor rotation. This function is effective regardless of
the specification of operation command input device (e.g., control terminal or integrated
operator). If an operation command to drive the motor in a restricted direction is given,
the inverter (display) shows (
).
Reverse run protection:
–
The reverse run protection function is effective when
“
(sensorless vector control)” or “
(0-SLV)” is specified for the V/F characteristic
selection (
). For control reasons, especially during motor operation at low speed, the
inverter may output a frequency that instructs the motor to rotate in the direction
opposite to that specified by the operation command.
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data Units
Rotation direction
restriction
Three option codes:
No restriction
Reverse rotation is restricted
Forward rotation is restricted
Reverse run protection
Two option codes:
No protection
Reverse rotation is protected
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...