Ver.3
−
−
−
−
21
(2)
Electronic Thermal Accumulation Gain
Only for accumulation for motor electronic thermal protection, value to accumulate is multiplied with
electronic thermal accumulation gain (b913) instead of standard value. When b910=00 and common to
inverter protection, b913 is void.
(3)
Electronic Thermal Function for inverter
When electronic thermal protection subtraction selection (b910) is set other than 0, electronic
thermal protection for inverter and motor are separated. Electronic thermal protection for inverter in
this case is as described below.
①
Thermal protection characteristics for inverter is fixed
(
Identical to the electronic thermal protection before Ver.3.0 with constant torque characteristics
with thermal level b012 with rated current
)
②
Characteristics are independent from b012-b020 setting therefore. (only for electronic thermal
protection for Motor is valid)
③
To be remarked that dual rating is considered. (it follows to CT/VT time constant)
④
Error code for inverter’s electronic thermal protection is E38 (inverter thermal protection). (Error
code for motor electronic thermal protection remains to be E05)
E38 trip cannot be reset for 10 seconds, identical to E05.
⑤
Subtraction is invalid for inverter electronic thermal protection.
When b910=0, electronic thermal protection for inverter and motor is common. (same before
Ver.3.0)
Following Table is summery of electronic thermal protection according to b910 setting
IRDY old/new spec. selection
•
With the inverter which there is parameter C900 in ON condition of the IRDY signal,
It can be selected whether GS1/GS2 signal is added by that parameter.
Code
Name
Description
Initial data
C
C
C
C9
9
9
900
00
00
00
IRDY action selection
00
00
00
00
…Before Ver. 3.0
0
0
0
01
1
1
1
…Ver. 3.0 or after
If you set “01
:
Ver. 3.0 or after”,
“GS1 and GS2
Both Close (operation possible side)”
is added to condition of IRDY turning
ON as “Logical product”.
01
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...