6
4
Safety function is enabled and either
GS1 or GS2 input is inactive.
If safety function is used, activate both GS1 and GS2. If
not, disable safety function by dip switch.
Possible Cause(s)
Corrective Action
"18:RS", "14:CS" or "11:FRS" is set to
input terminal and the input is active.
Deactivate the input.
"84:ROK" is set to input terminal and
the input is active.
Activate the input.
Cable between inverter and motor or
internal cable of motor is breaking.
Check the wiring.
Excess load.
Remove excess load.
Motor is locked.
Unlock the motor.
3. Motor does not accelerate to command speed.
Possible Cause(s)
Corrective Action
Bad connection of analog wiring.
Check the wiring.
In case of analog voltage or variable resistor input, check
voltage between [O] and [L] terminal.
In case of analog current, check current between current
source and [OI] terminal.
Overload restriction or OC suppression
function works.
Check the function level.
Max. frequency (A004) or upper limit
(A061/A261) is lower than as expected.
Check the value.
Acceleration time is excessive.
Change acceleration time (F002/A092/A292).
“Multi-speed input(s) (02 to 05:CF1 to
CF4)” is (are) set to input terminal(s)
and active.
Deactivate the input(s).
"06:JG " is set to input terminal and the
input is active.
Deactivate the input.
Excess load.
Remove excess load.
Motor is locked.
Unlock the motor.
4. Inverter does not respond to changes in frequency setting from operator.
Possible Cause(s)
Corrective Action
Incorrect frequency source is selected.
Check frequency source (A001=02).
"51:F-TM" is set to input terminal and
the input is active.
Deactivate the input.
5. A part of function codes is not displayed.
Possible Cause(s)
Corrective Action
"Function code display restriction" (b037)
is enabled.
Set 00 (all display) to b037.
"86:DISP" is set to input terminal and
the input is active.
Deactivate the input.
6. Operator (keypad) does not respond.
Possible Cause(s)
Corrective Action
"86:DISP" is set to input terminal and
the input is active.
Deactivate the input.
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...