“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
A
B
Initial data
Units
Torque limit 3 (rev/power)
Torque limit level in reverse powering
quadrant, range is 0 to 200%/no(disabled)
200
%
Torque limit 4 (fwd/regen.)
Torque limit level in forward regen.
quadrant, range is 0 to 200%/no(disabled)
200
%
Torque LAD STOP selection
Two option codes:
Disable
Enable
00
Reverse run protection
Two option codes:
No protection
Reverse rotation is protected
00
Dual Rating Selection
(CT mode) /
(VT mode)
00
Controlled deceleration on
power loss
Four option codes:
Trips
Decelerates to a stop
Decelerates to a stop with DC bus
voltage controlled
Decelerates to a stop with DC bus
voltage controlled, then restart
00
DC bus voltage trigger level
of ctrl. decel.
Setting of DC bus voltage to start
controlled decel. operation. Range is 0.0
to 1000.0
220.0/
440.0
V
Over-voltage threshold of
ctrl. decel.
Setting the OV-LAD stop level of
controlled decel. operation. Range is 0.0
to 1000.0
360.0/
720.0
V
Deceleration time of ctrl.
decel.
Range is 0.01 to 3600.0 seconds.
1.00
s
Initial freq. drop of ctrl.
decel.
Setting of initial freq. drop.
Range is 0.0 to 10.0 Hz
0.00
Hz
Maximum-limit level of
window comparator (O)
Set range, {Min.-limit level (
) +
hysteresis width (
)x2} to 100 %
(Minimum of 0%)
100.
%
Minimum-limit level of
window comparator (O)
Set range, 0 to {Max.-limit level (
) -
hysteresis width (
)x2} % (Maximum
of 0%)
0.
%
Hysteresis width of window
comparator (O)
Set range, 0 to {Max.-limit level (
) -
Min.-limit level (
)}/2 % (Maximum of
10%)
0.
%
Maximum-limit level of
window comparator (OI)
Set range, {Min.-limit level (
+
hysteresis width (
)x2} to 100 %
(Minimum of 0%)
100.
%
Minimum-limit level of
window comparator (OI)
Set range, 0 to {Max.-limit level (
) -
hysteresis width (
)x2} % (Maximum
of 0%)
0.
%
Hysteresis width of window
comparator (OI)
Set range, 0 to {Max.-limit level (
) -
Min.-limit level (
)}/2 % (Maximum of
10%)
0.
%
Operation level at O
disconnection
Set range, 0 to 100%, or “no” (ignore)
no
-
Operation level at OI
disconnection
Set range, 0 to 100%, or “no” (ignore)
no
-
Ambient temperature setting Set range is,
-10~50
C
40
C
Watt-hour clearance
Two option codes:
OFF
ON (press STR then clear)
00
-
Watt-hour display gain
Set range is,
1.~1000.
1.
Start frequency
Sets the starting frequency for the
inverter output, range is 0.10 to 9.99 Hz
0.50
Hz
Carrier frequency
Sets the PWM carrier (internal switching
frequency), range is 2.0 to 15.0 kHz
10.0
kHz
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...