B
25
Coil No.
Item
R/W
Setting
002Dh
OL2 (overload notice advance (2))
R
1: ON, 0: OFF
002Eh
Odc: Analog O disconnection
detection
-
1: ON, 0: OFF
002Fh
OIDc: Analog OI disconnection
detection
-
1: ON, 0: OFF
0030h
(Reserved)
-
-
0031h
(Reserved)
-
-
0032h
FBV (PID feedback comparison)
R
1: ON, 0: OFF
0033h
NDc (communication train
disconnection)
R
1: ON, 0: OFF
0034h
LOG1 (logical operation result 1)
R
1: ON, 0: OFF
0035h
LOG2 (logical operation result 2)
R
1: ON, 0: OFF
0036h
LOG3 (logical operation result 3)
R
1: ON, 0: OFF
0037h
(Reserved)
-
-
0038h
(Reserved)
-
-
0039h
(Reserved)
-
-
003Ah
WAC (capacitor life warning)
R
1: ON, 0: OFF
003Bh
WAF (cooling-fan speed drop)
R
1: ON, 0: OFF
003Ch
FR (starting contact signal)
R
1: ON, 0: OFF
003Dh
OHF (heat sink overheat warning)
R
1: ON, 0: OFF
003Eh
LOC (low-current indication signal)
R
1: ON, 0: OFF
003Fh
M01 (general output 1)
R
1: ON, 0: OFF
0040h
M02 (general output 2)
R
1: ON, 0: OFF
0041h
M03 (general output 3)
R
1: ON, 0: OFF
0042h
(Reserved)
-
-
0043h
(Reserved)
-
-
0044h
(Reserved)
-
-
0045h
IRDY (inverter ready)
R
1: ON, 0: OFF
0046h
FWR (forward rotation)
R
1: ON, 0: OFF
0047h
RVR (reverse rotation)
R
1: ON, 0: OFF
0048h
MJA (major failure)
R
1: ON, 0: OFF
0049h
Data writing in progress
R
1: Writing in progress, 0: Normal status
004Ah
CRC error
R
1: Error detected, 0: No error (*2)
004Bh
Overrun
R
1: Error detected, 0: No error (*2)
004Ch
Framing error
R
1: Error detected, 0: No error (*2)
004Dh
Parity error
R
1: Error detected, 0: No error (*2)
004Eh
Sum check error
R
1: Error detected, 0: No error (*2)
004Fh
(Reserved)
-
-
0050h
WCO (window comparator O)
R
1: ON, 0: OFF
0051h
WCOI (window comparator OI)
R
1: ON, 0: OFF
0052h
(Reserved)
-
-
0053h
OPDc (option disconnection)
R
1: ON, 0: OFF
0054h
FREF (FQ command source)
R
1: Operator, 0: Others
0055h
REF (RUN command source)
R
1: Operator, 0: Others
0056h
SETM (2nd motor selected)
R
1: 2nd motor selected, 0: 1st motor selected
0057h
(Reserved)
-
-
0058h
EDM (Gate suppress monitor)
R
1: ON, 0: OFF
0059h-
unused
R
inaccessible
*1 Normally, this coil is turned on when the corresponding intelligent input terminal on the control
circuit terminal block is turned on or the coil itself is set to on. In this regard, the operation of
the intelligent input terminal has priority over the operation of the coil. If disconnection of the
communication train has disabled the master system from turning off the coil, turn the
corresponding intelligent input terminal on the control circuit block on and off. This operation
turns off the coil.
*2 Communication error data is retained until an error reset command is input. (The data can be
reset during the inverter operation.)
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...