Ver.3
−
−
−
−
6
Over-current Trip Suppression: b027 -
The Over-current Trip Suppression function monitors the motor
current and actively changes the output frequency profile to
maintain the motor current within the limits. Although “LAD”
refers to “linear acceleration / deceleration”, the inverter only
“STOPs” the acceleration and deceleration ramp so that it will not
cause an over-current trip event.
The graph at right shows an inverter output profile that starts
acceleration to a constant speed. At two different points during the
acceleration, motor current increases and exceeds the fixed level of
Over-current Trip Suppression level.
When the Over-current Trip Suppression feature is enabled by b
b
b
b0
0
0
02
2
2
27
7
7
7 = 0
0
0
01
1
1
1/0
0
0
02
2
2
2, the inverter stops the
acceleration ramp in each case until the motor current level is again less than the threshold value, which
is approximately 180% of the rated current of the inverter.
When using the Over-current Trip Suppression feature, please note the following:
•
When the feature is enabled (b
b
b
b0
0
0
02
2
2
27
7
7
7 = 0
0
0
01
1
1
1/0
0
0
02
2
2
2), the actual acceleration may be longer than the value
set by parameters F
F
F
F00
00
00
002
2
2
2/F
F
F
F2
2
2
20
0
0
02
2
2
2 in some cases.
•
The Over-current Trip Suppression feature does not operate by maintaining a constant motor
current, so it does not prevent Over-current Trip events completely. Over-current trip event may
happen during extreme acceleration or by the short-circuit states for example.
•
When b
b
b
b0
0
0
02
2
2
27
7
7
7
set to "0
0
0
02
2
2
2
…
Enable with voltage reduction", the Over-current Trip Suppression function
raises the effect by reducing output voltage after an acceleration and deceleration halt. Following
are the related parameters for this function.
Func.
Func.
Func.
Func.
Code
Code
Code
Code
Name
Name
Name
Name
Descrip
Descrip
Descrip
Description
tion
tion
tion
b
b
b
b0
0
0
02
2
2
27
7
7
7
OC suppression selection
00
00
00
00
…
Disabled
0
0
0
01
1
1
1
…
Enabled without voltage
reduction
0
0
0
02
2
2
2
…
Enable with voltage
reduction
(Added by Ver.3.0)
Motor
0
t
Output
0
t
Stops accel
Resumes accel
B027
B027
B027
B027
=
01
01
01
01
/
02
02
02
02
OC LAD STOP = Enabled
Set acc time (
F002
F002
F002
F002
)
Actual acc time
Approx. 150% of the inverter
rated current
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...