C
−
−
−
−
20
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
A B Initial data Units
b106
Free V/F setting, freq.4
Set range, value of
b104
~
b108
0.
Hz
b107
Free V/F setting, voltage.4
Set range, 0 ~ 800V
0.0
V
b108
Free V/F setting, freq.5
Set range, value of
b108
~
b110
0.
Hz
b109
Free V/F setting, voltage.5
Set range, 0 ~ 800V
0.0
V
b110
Free V/F setting, freq.6
Set range, value of
b108
~
b112
0.
Hz
b111
Free V/F setting, voltage.6
Set range, 0 ~ 800V
0.0
V
b112
Free V/F setting, freq.7
Set range,
b110
~ 400
0.
Hz
b113
Free V/F setting, voltage.7
Set range, 0 ~ 800V
0.0
V
B120
Brake control enable
Two option codes:
00
…
Disable
01
…
Enable
00
-
b121
Brake Wait Time for Release Set range: 0.00 to 5.00 sec
0.00
Sec
b122
Brake Wait Time for
Acceleration
Set range: 0.00 to 5.00 sec
0.00
Sec
b123
Brake Wait Time for
Stopping
Set range: 0.00 to 5.00 sec
0.00
Sec
b124
Brake Wait Time for
Confirmation
Set range: 0.00 to 5.00 sec
0.00
Sec
b125
Brake release freq.
Set range: 0 to 400Hz
0.00
Sec
b126
Brake release current
Set range: 0~200% of inverter
rated current
(rated
current)
A
b127
Braking freq. setting
Set range: 0 to 400Hz
0.00
Hz
B130
Deceleration overvoltage
suppression enable
00
…
Disabled
01
…
Enabled
02
…
Enabled with accel.
00
−
B131
Decel. overvolt. suppress
level
DC bus voltage of suppression.
Range is:
200V class
…
330 to 395
400V class
…
660 to 790
380
/760
V
b132
Decel. overvolt. suppress
const.
Accel. rate when b130=02.
Set range: 0.10 ~ 30.00 sec.
1.00
sec
B133
Decel. overvolt. suppress
proportional gain
Proportional gain when b130=01.
Range is: 0.00 to 5.00
0.20
−
B134
Decel. overvolt. suppress
integral time
Integration time when b130=01.
Range is: 0.00 to 150.0
1.0
sec
b145
GS input mode
Two option codes:
00
…
No trip (Hardware shutoff
only)
01
…
Trip
00
-
b150
Display ex.operator
connected
When an external operator is
connected via RS-422 port, the
built-in display is locked and shows
only one "d" parameter configured
in:
d001
~
d030
001
−
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...