Low Load Detection Parameters
The following parameters work in
conjunction with the intelligent output
function, when configured. The output
mode parameter (
) sets the mode of
the detection at which the low load
detection signal [LOC] turns ON. Three
kinds of modes can be selected. The
detection level parameter (
) is to set
the level of the low load.
This function is for generating an early
warning logic output, without causing
either a trip event or a restriction of the
motor current (those effects are available
on other functions).
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
Output mode of low
current detection
Two option codes:
During acceleration,
deceleration and constant speed
During constant speed only
01
Low current detection
level
Set the level of low load detection,
range is 0.0 to 2.0*inverter rated
current
INV rated
current
A
Output
current
[LOC]
output
0
1
0
t
t
ON
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...