Internal Relay Output
The inverter has an internal relay output with
normally open and normally closed contacts
(Type 1 form C). The output signal that
controls the relay is configurable; the Alarm
Signal is the default setting. Thus, the
terminals are labeled [AL0], [AL1], [AL2], as
shown to the right. However, you can assign
any one of the nine intelligent outputs to the
relay. For wiring purposes, the general
terminal functions are:
[AL0] – Common contact
[AL1] – Normally open contact
[AL2] – Normally closed contact
The relay itself can be configured as “normally open or closed.” Parameter
, Alarm
Relay Active State, is the setting. This setting determines whether or not the relay coil
is energized when its output signal is OFF:
=
– “Normally open” (relay coil is de-energized when output signal is OFF)
=
– “Normally closed” (relay coil is energized when the output signal is OFF)
Since the relay already has normally open
[AL1] and normally closed [AL2] contacts, the
purpose of the ability to invert the relay coil’s
active state may not be obvious.
It allows you to
determine whether or not an inverter power
loss causes the relay to change state.
The
default relay configuration is the Alarm Signal
(
=
), as shown to the right. And,
=
sets the relay to “normally closed” (relay coil
normally energized). The reason for this is that
a typical system design will require an inverter
power loss to assert an alarm signal to external
devices.
The relay can be used for other intelligent
output signals, such as the Run Signal (set
=
). For these remaining output signal
types, the relay coil typically must NOT change
state upon inverter power loss (set
=
).
The figure to the right shows the relay settings
for the Run Signal output.
If you assign the relay an output signal other
than the Alarm Signal, the inverter can still
have an Alarm Signal output. In this case, you
can assign it to terminal [11] , providing an
open collector output.
AL1
AL0
AL2
Inverter logic
circuit board
AL1
AL0
AL2
Inverter logic
circuit board
=
=
Relay shown with inverter
power ON, Run Signal OFF
RUN
AL1
AL0
AL2
Inverter logic
circuit board
=
=
Relay shown with inverter
power ON, Alarm Signal OFF
AL
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...