![Hitachi WJ200-001L Скачать руководство пользователя страница 619](http://html.mh-extra.com/html/hitachi/wj200-001l/wj200-001l_instruction-manual_140877619.webp)
Ver.3
−
−
−
−
110
Register
No.
Function name
Function
code
R/W
Monitoring and setting items
Data
resolution
1633h
Motor poles setting for RPM
P049
R/W
0 (0 pole), 1 (2 poles), 2 (4 poles), 3 (6 poles),
4 (8 poles), 5 (10 poles), 6 (12 poles), 7 (14 poles),
8 (16 poles), 9 (18 poles), 10 (20 poles), 11 (22 poles),
12 (24poles), 13 (26 poles), 14 (28 poles),
15 (30 poles), 16 (32 poles), 17 (34 poles),
18 (36 poles), 19 (38 poles), 20 (40 poles),
21 (42 poles), 22 (44poles), 23 (46 poles),
24 (48 poles)
-
1634h to
1638h
(Reserved)
-
-
-
-
1639h
Pulse train frequency scale
P055
R/W
10 to 320 (input frequency corresponding to the
allowable maximum frequency)
0.1 [kHz]
163Ah
Time constant of pulse train
frequency filter
P056
R/W 1 to 200
0.01 [s]
163Bh
Pulse train frequency bias
P057
R/W -100 to +100
1 [%]
163Ch
Pulse train frequency limit
P058
R/W 0 to 100
1 [%]
163Dh
Lower cut off level of the input
pulse
*2
P059
R/W 1 to 2000
0.01[%]
163Eh
Multistage position 0
P060(HIGH)
R/W
1
163Fh
P060(LOW)
R/W
1640h
Multistage position 1
P061(HIGH)
R/W
1
1641h
P061(LOW)
R/W
1642h
Multistage position 2
P062(HIGH)
R/W
1
1643h
P062(LOW)
R/W
1644h
Multistage position 3
P063(HIGH)
R/W
1
1645h
P063(LOW)
R/W
1646h
Multistage position 4
P064(HIGH)
R/W
1
1647h
P064(LOW)
R/W
1648h
Multistage position 5
P065(HIGH)
R/W
1
1649h
P065(LOW)
R/W
164Ah
Multistage position 6
P066(HIGH)
R/W
1
164Bh
P066(LOW)
R/W
164Ch
Multistage position 7
P067(HIGH)
R/W
1
164Dh
P067(LOW)
R/W
164Eh
Homing mode selection
P068
R/W 0(Low) / 1(High)
164Fh
Homing direction
P069
R/W 0(FW) / 1(RV)
1650h
Low-speed homing frequency
P070
R/W 0 to 1000
1651h
High-speed homing frequency
P071
R/W 0 to 40000
1652h
Position range (forward)
P072(HIGH)
R/W
0 to 268435455
1
1653h
P072(LOW)
R/W
1654h
Position range (reverse)
P073(HIGH)
R/W
-268435455 to 0
1
1655h
P073(LOW)
R/W
1656h
(Reserved),
-
-
-
-
1657h
Positioning mode
P075
R/W
00…With limitation
01…No limitation (fastest control)
1658h
(Reserved),
-
-
-
-
1659h
Encoder disconnection timeout
P077
R/W 0 to 100
0.1[s]
165Ah to
165Bh
(Reserved),
-
-
-
-
165Ch
Positioning restart range
*2
P080
R/W 0 to 10000
1[pulse]
165Dh
Store position at power off
selection
*2
P081
R/W
0: Not store,
1: Store
-
165Eh
Current position at power off
*2
P082(HIGH)
R
P073 to P072
1
165Fh
P082(LOW)
R
1660h
Preset position data
*2
P083(HIGH)
R/W
P073 to P072
1
1661h
P083(LOW)
R/W
1662h to
1665h
(Reserved)
-
-
-
-
*2
: Available from version 3.0
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...