4
90
Analog Output Operation
In inverter applications it is useful to monitor the
inverter operation from a remote location or from the
front panel of an inverter enclosure. In some cases,
this requires only a panel-mounted volt meter. In
other cases, a controller such as a PLC may provide
the inverter’s frequency command, and require
inverter feedback data (such as output frequency or
output current) to confirm actual operation. The
analog output terminal [AM] serves these purposes.
The inverter provides an analog voltage output on terminal [AM] with terminal [L] as
analog GND reference. The [AM] can output inverter frequency or current output value.
Note that the voltage range is 0 to +10V (positive-going only), regardless of forward or
reverse motor rotation. Use
to configure terminal [AM] as indicated below.
Func.
Code
Description
Inverter output frequency
Inverter output current
Inverter output torque
Digital output freqnency
Inverter output goltage
Inverter input power
Electronic Thermal Load
LAD frequency
Digital current monitor
Cooling fin temperature
General purpose
Pulse train
Option
AM H O OI L
+
-
A GND
Analog
Voltage
Output
10VDC
full scale,
2mA max
See I/O specs on page4-6
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...