4
20
External Signal for DC Braking
When the terminal [DB] is turned ON, the
DC braking feature is enabled. Set the
following parameters when the external DC
braking terminal [DB] is to be used:
– DC braking delay time setting.
The range is 0.1 to 5.0 seconds.
– DC braking force setting. The
range is 0 to 100%.
The scenarios to the right help show how DC
braking works in various situations.
1. Scenario 1 – The [FW] or [RV] terminal is
ON. When [DB] is ON, DC braking is
applied. When [DB] is OFF again, the
output frequency ramps to the prior level.
2. Scenario 2 – The Run command is applied
from the operator keypad. When the [DB]
terminal is ON, DC braking is applied.
When the [DB] terminal is OFF again, the
inverter output remains OFF.
3. Scenario 3 – The Run command is applied
from the operator keypad. When the [DB]
terminal is ON, DC braking is applied
after the delay time set by
expires.
The motor is in a free-running (coasting)
condition. When the [DB] terminal is OFF
again, the inverter output remains OFF.
Option
Code
Terminal
Symbol
Function Name
State
Description
DB
External DC
Braking
ON
Applies DC injection braking during deceleration
OFF
Does not apply DC injection braking during
deceleration
Valid for inputs:
~
Example (requires input configuration
—see
page 3-85
):
See I/O specs on
page 4
–6.
Required settings
,
Notes:
Do not use the [DB] input continuously or for a
long time when the DC braking force setting
is high (depends on the motor application).
Do not use the [DB] feature for continuous or high
duty cycle as a holding brake. The [DB] input is
designed to improve stopping performance. Use a
mechanical brake for holding a stop position.
[FW,RV]
1
0
[DB]
1
0
Output
frequency
Scenario 1
t
Run command
from operator
1
0
[DB]
1
0
Output
frequency
Scenario 2
t
Run command
from operator
1
0
[DB]
1
0
Output
frequency
Scenario 3
t
delay
DB
7
6
5
4
3
2
1
L
P24
PLC
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...