CAUTION: Be careful to avoid specifying a braking time that is long enough to cause
motor overheating. If you use DC braking, we recommend using a motor with a built-in
thermistor, and wiring it to the inverter’s thermistor input (see “Thermistor Thermal
Protection” in chapter 4). Also refer to the motor manufacturer’s specifications for
duty-cycle recommendations during DC braking.
DC braking performance at start can also be set separately (
and
).
And carrier frequency of DC braking performance can also be set separately (
).
CAUTION: Be careful to avoid specifying a braking carrier frequency that is high
enough to cause inverter and motor overheating. If you use DC braking, we recommend
using a motor with a built-in thermistor, and wiring it to the inverter’s thermistor input
(see “Thermistor Thermal Protection” in chapter 4). Also refer to the motor
manufacturer’s specifications for duty-cycle recommendations during DC braking.
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
DC braking enable
Three options; select codes:
Disable
Enable during stop
Frequency detection
The frequency at which DC
braking begins,
range is from the start
frequency (
) to 60Hz
00
DC braking frequency
0.5
Hz
DC braking wait time
The delay from the end of
controlled deceleration to start
of DC braking (motor free runs
until DC braking begins),
range is 0.0 to 5.0 sec.
Level of DC braking force,
settable from 0 to 100%
0.0
sec.
DC braking force for
deceleration
50.
%
DC braking time for
deceleration
Sets the duration for DC
braking, range is from 0.0 to
60.0 seconds
0.5
sec.
DC braking / edge or level
detection for [DB] input
Two options; select codes:
Edge detection
Level detection
01
DC braking force at start
Level of DC braking force at
start, settable from 0 to 100%
0.
%
DC braking time at start
Sets the duration for DC
braking, range is from 0.0 to
60.0 seconds
0.0
sec.
Carrier frequency during DC
braking
Carrier frequency of DC
braking performance, range is
from 2.0 to 15.0kHz
5.0
sec.
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...