Analog Input Signal Calibration Settings
The functions in the following table
configure the signals for the analog input
terminals. Note that these settings do not
change the current/voltage or sink/source
characteristics – only the zero and span
(scaling) of the signals.
These parameters are already adjusted
before the shipment, and therefore it is
not recommended to do the adjustment at
the customer.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
O input span calibration
Scale factor between the external
frequency command on terminals
L–O (voltage input) and the
frequency output,
range is 0.0 to 200%
100.0
%
OI input span calibration Scale factor between the external
frequency command on terminals
L–OI (voltage input) and the
frequency output,
range is 0.0 to 200%
100.0
%
Thermistor input (PTC)
span calibration
Scale factor of PTC input.
Range is 0.0 to 200%
100.0
%
NOTE: When you restore factory default settings, the values will change to those listed
above. Be sure to manually reconfigure the values for your application, if needed, after
restoring factory defaults.
Max. freq
Max. freq /2
10V, 20mA
5V, 12mA
200%
100%
50%
0
0V, 4mA
Freq setpoint
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...