Ver.2
56
Fine Tuning Functions
NOTE:. Mark “
” in A line of [ Run Mode Edit] shows the accessible parameters when b031 is not set “10”,
high level access.
NOTE:. Mark “
” in B line of [ Run Mode Edit] shows the accessible parameters when b031 is set “10”,
high level access
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
A
B
Initial data
Units
Restart mode on power
failure / under-voltage trip
Select inverter restart method,
Five option codes:
Alarm output after trip, no
automatic restart
Restart at 0Hz
Resume operation after frequency
matching
Resume previous freq. after freq.
matching, then decelerate to stop and
display trip info
Resume operation after active freq.
matching
00
Allowable under-voltage
power failure time
The amount of time a power input
under-voltage can occur without tripping
the power failure alarm. Range is 0.3 to
25 sec. If under-voltage exists longer than
this time, the inverter trips, even if the
restart mode is selected.
1.0
s
Retry wait time before motor
restart
Time delay after under-voltage condition
goes away, before the inverter runs motor
again.
Range is 0.3 to 100 seconds.
1.0
s
Instantaneous power failure
/ under-voltage trip alarm
enable
Three option codes:
Disable
Enable
Disable during stop and decelerates
to a stop
00
Number of restarts on power
failure / under-voltage trip
events
Two option codes:
Restart 16 times
Always restart
00
Restart frequency threshold
Restart the motor from 0Hz if the
frequency becomes less than this set
value during the motor is coasting, range
is 0 to 400Hz
0.00
Hz
Restart mode on over voltage
/ over current trip
Select inverter restart method,
Five option codes:
Alarm output after trip, no
automatic restart
Restart at 0Hz
Resume operation after frequency
matching
Resume previous freq. after active
freq. matching, then decelerate to
stop and display trip info
Resume operation after active freq.
matching
00
Number of retry on over
voltage / over current trip
Range is 1 to 3 times
3
Retry wait time on over
voltage / over current trip
Range is 0.3 to 100 sec.
1.0
s
Level of electronic thermal
Set a level between 20% and 100% for the
Rated
A
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...