B
33
Register
No.
Function name
Function code
R/W
Monitoring and setting items
Data
resolution
124Fh
Frequency upper limit
A061 (high)
R/W 0 or "maximum frequency limit" to
"maximum frequency"
0.01 [Hz]
1250h
A061 (low)
R/W
1251h
Frequency lower limit
A062 (high)
R/W 0 or "maximum frequency limit" to
"maximum frequency"
0.01 [Hz]
1252h
A062 (low)
R/W
1253h
Jump freq. (center) 1
A063 (high)
R/W
0 to 40000(100000)
0.01 [Hz]
1254h
A063 (low)
R/W
1255h
Jump freq. width
(hysteresis) 1
A064
R/W 0 to 1000(10000)
0.01 [Hz]
1256h
Jump freq. (center) 2
A065 (high)
R/W
0 to 40000(100000)
0.01 [Hz]
1257h
A065 (low)
R/W
1258h
Jump freq. width
(hysteresis) 2
A066
R/W 0 to 1000(10000)
0.01 [Hz]
1259h
Jump freq. (center) 3
A067 (high)
R/W
0 to 40000(100000)
0.01 [Hz]
125Ah
A067 (low)
R/W
125Bh
Jump freq. width
(hysteresis) 3
A068
R/W 0 to 1000(10000)
0.01 [Hz]
125Ch
Acceleration hold frequency
A069 (high)
R/W
0 to 40000
0.01 [Hz]
125Dh
A069 (low)
R/W
125Eh
Acceleration hold time
A070
R/W 0 to 600
0.1 [sec.]
125Fh
PID Function Enable
A071
R/W
0 (disabling), 1 (enabling), 2 (enabling
inverted-data output)
-
1260h
PID proportional gain
A072
R/W 0 to 2500
0.10
1261h
PID integral time constant
A073
R/W 0 to 36000
0.1 [sec.]
1262h
PID derivative gain
A074
R/W 0 to 10000
0.01 [sec.]
1263h
PV scale conversion
A075
R/W 1 to 9999
0.01
1264h
PV source
A076
R/W
0 (input via OI), 1 (input via O), 2 (external
communication), 3 (pulse train frequency
input), 10 (operation result output)
-
1265h
Reverse PID
A077
R/W 00 (disabling), 01 (enabling)
-
1266h
PID output limiter
A078
R/W 0 to 1000
0.1 [%]
1267h
PID feed forward selection
A079
R/W 0 (disabled), 1(O input), 2 (OI input)
-
1268h
(Reserved)
-
R/W -
-
1269h
AVR function select
A081
R/W
0 (always on), 1 (always off), 2 (off during
deceleration)
-
126Ah
AVR voltage select
A082
R/W
200 V class: 0 (200)/1 (215)/2 (220)/3
(230)/4 (240)
400 V class: 5 (380)/6 (400)/7 (415)/8
(440)/9 (460)/ 10 (480)
-
126Bh
AVR filter time constant
A083
R/W 0.000 to 10.00
0.001[sec]
126Ch
AVR deceleration gain
A084
R/W 50 to 200
1[%]
126Dh
Energy-saving operation
mode
A085
R/W
0 (normal operation), 1 (energy-saving
operation)
-
126Eh
Energy-saving mode tuning
A086
R/W 0 to 1000
0.1 [%]
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...