![Hitachi WJ200-001L Скачать руководство пользователя страница 98](http://html.mh-extra.com/html/hitachi/wj200-001l/wj200-001l_instruction-manual_140877098.webp)
3
13
Run Command Source Setting
–
For parameter
, the following table provides a
further description of each option, and a reference to other page(s) for more information.
Code
Run Command Source
Refer to page(s)
…
Control terminal
– The [FW] or [RV] input terminals control
Run/Stop operation
4-16
Keypad Run key
– The Run and Stop keys provide control
2-23
ModBus network input
– The network has a dedicated coil for
Run/Stop command and a coil for FW/RV
B-24
Option
– Select when an option card is connected and use the
frequency source from the option
(manual of each
option)
/
Override Sources
–
The inverter allows some sources to override the setting
for output frequency and Run command in
and
. This provides flexibility for
applications that occasionally need to use a different source, leaving the standard
settings in
/
.
The inverter has other control sources that can temporarily override the parameter
setting, forcing a different output frequency source. The following table lists all
frequency source setting methods and their relative priority (“1” is the highest priority).
Priority
Frequency Source Setting Method
Refer to page
…
1
[CF1] to [CF4] Multi-speed terminals
4-17
2
[OPE] Operator Control intelligent input
4-35
3
[F-TM] intelligent input
4-42
4
[AT] terminal
4-28
5
Frequency source setting
3-10
The inverter also has other control sources that can temporarily override the parameter
setting, forcing a different Run command source. The following table lists all Run
command setting methods and their relative priority (“1” is the highest priority).
Priority
Run Command Setting Method
Refer to page
…
1
[OPE] Operator Control intelligent input
4-35
2
[F-TM] intelligent input
4-42
3
Run command source setting
3-10
Содержание WJ200-001L
Страница 2: ......
Страница 3: ......
Страница 49: ......
Страница 63: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 299: ......
Страница 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Страница 305: ......
Страница 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 387: ......
Страница 509: ......
Страница 552: ...Ver 3 43 External register number 1218h A021 HIGH 1219h A021 Low Internal register number 120Fh A013 Access Denied ...
Страница 665: ......
Страница 673: ......
Страница 674: ...Index 1 Index Index page A B C 2 D E F G H 3 I J K L M 4 N O P 5 Q R S 6 T U V W X Y Z 7 Index ...