Configuring the Built-in Ethernet Port
The built-in Ethernet port must be properly configured to communicate on a
network or directly with a PC. The Ethernet port has been factory set as follows:
•
IP Address
: 192.168.000.001
•
Telnet (Set-up) Port
: 9999
•
Web Manager (Set-up) Port
: 30718 (Fixed)
•
Serial Data Port
: 10001
The configuration is stored in nonvolatile memory and is retained without
power. The configuration can be changed at any time.
If the IP address or any other setting needs to be changed, the Ethernet port
Setup Mode
can be accessed using a Telnet connection, the Web Manager
locally or over the network.
To configure the built‐in Ethernet port with Telnet
1.
From your computer Windows desktop, click
Start
followed by
Run
(usually located in the lower right side of the
Start Menu
).
2.
Type the following command:
telnet 192.168.000.001 9999
3.
Click
OK
to establish a Telnet connection. The following message
appears:
MAC address XXXXXXXXXXXX
(E.g., 00204A808BE8)
Software version
V6.3.0.3RC3 (061110)
(Version may vary by system)
Press Enter for Setup Mode
4.
To enter
Setup Mode
, press
Enter
within 5 seconds. The
configuration settings display, followed by the
Change Setup
menu.
Change Setup:
0 Server
1 Channel 1
5 Expert
6 Security
7 Defaults
8 Exit without save
9 Save and exit
Your choice?
5.
Select an option on the menu by entering the number of the option
in the “Your choice?” field and pressing
Enter
.
The two menus recommended for review are “0 Server” and “1
Channel 1”. Bypass the other options listed in the menu.
Содержание SpectraSensors SS2000e
Страница 2: ......
Страница 4: ......
Страница 8: ...NS 5 14 Firmware iv 4900002262 rev B 3 23 21 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 10: ...NS 5 14 Firmware vi 4900002262 rev B 3 23 21 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 12: ...NS 5 14 Firmware viii 4900002262 rev B 3 23 21 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 100: ...NS 5 14 Firmware 4 10 4900002262 rev B 3 23 21 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 106: ...NS 5 14 Firmware A 6 4900002262 rev B 3 23 21 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 112: ...NS 5 14 Firmware Index 6 4900002262 rev A 3 23 21 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 113: ......
Страница 114: ...www spectrasensors com contact 4900002262 Rev B...