Operation
Liquiline System CA80NO
78
Hauser
Utilize the advantage of the effectively wear-free control with binary outputs versus a
control system with relay. With pulse frequency modulation (PFM), it is possible to achieve
virtually continuous dosing using a dosing pump with higher input frequency.
1. Connect the INS proximity switch of the CCA250 assembly to a digital input of the
DIO module (e.g. slot 6, port 1).
2. In the software, configure a controller and as the source select the binary input
(e.g.
Binary input 1
) to which the proximity switch is connected. (
Menu
/
Additional
functions
/
Controllers
/
Controller 1
/
Controller Enable
=
Binary input 1
)
3.
Signal type
: For the selected input, select the factory setting (
Static signal
).
4. Connect the measured value of a flowmeter to the second input of the DIO module
(e.g. slot 6, port 2).
5.
Signal type
: for this input, select
PFM
. (
Menu
/
Inputs
/
Binary input
6:2
/
Signal
type
=
PFM
)
6.
Input variable
: select the corresponding measured value (
Flow rate
).
You can now use the input you have just configured as the disturbance variable
for your controller
7.
Disturbance variable
: in the controller menu, select the binary input to which you
have connected the flow measured value. (
Menu
/
Additional functions
/
Controllers
/
Controller 1
/
Disturbance variable
/
Source of data
=
Binary input
6:2
and
Measured value
=
PFM value
)
8. You can activate a dosing pump through PFM via a digital output of the DIO module.
Connect the pump to an output of the DIO module (e.g. slot 6, port 1) and select the
following settings in the menu:
Menu
/
Outputs
/
Binary output
6:1
/
Signal type
=
PFM
and
Source of data
=
Controller 1
.
Take the direction of action of your dosing into account. Select the correct parameter
(
Actuator type
=
U
or
Unipolar-
).
You must make additional settings in the controller menu to fully customize the control to
suit your process conditions.
CA80 as the cleaning master for connected sensors (optional)
CA80
47
48
91
92
1
2
3
Dig.in
CA80
CA80
A0029241
71
Example of a central cleaning control
1
External cleaning trigger at the binary input
2
Transferring the external hold over binary output to other measuring devices without connected cleaning
functions
3
Transferring the cleaning trigger over a binary output to other self-cleaning measuring points
1. An external trigger actuates a cleaning operation at the master.
A cleaning unit is connected via a relay or a binary output, for example.
2)
An activation code, Order No. 71211288, is necessary for the "feedforward control" function.
Содержание Liquiline System CA80NO
Страница 2: ......
Страница 116: ...Operation Liquiline System CA80NO 116 Endress Hauser 5 Connect the valve or pump ...
Страница 171: ......
Страница 172: ...www addresses endress com ...