Commissioning
Proline t-mass I 300 HART
90
Hauser
0/4 mA value
20 mA value
Fixed current
Terminal number
Damping output 1 to n
Failure mode
Terminal number
Failure current
Terminal number
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
interface / User
entry
Factory setting
Assign current output 1 to n
–
Select process variable for
current output.
• Off
• Temperature
• Mass flow
• Corrected volume
flow
• FAD volume flow
• Volume flow
• Energy flow
• Heat flow
• Density
• Flow velocity
• Pressure
• 2nd temperature
delta heat
• Electronic
temperature
–
Terminal number
–
Shows the terminal numbers
used by the current output
module.
• Not used
• 26-27 (I/O 1)
• 24-25 (I/O 2)
• 22-23 (I/O 3)
–
Current span
–
Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
• 4...20 mA (4...
20.5 mA)
• 0...20 mA (0...
20.5 mA)
• Fixed current
Country-specific:
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
Signal mode
–
Select the signal mode for the
current output.
• Active
• Passive
Active