Proline t-mass I 300 HART
Commissioning
Hauser
97
Parameter
Prerequisite
Description
Selection / User
interface / User
entry
Factory setting
Switch output function
The
Switch
option is selected
in the
Operating mode
parameter parameter.
Select function for switch
output.
• Off
• On
• Diagnostic
behavior
• Limit
• Flow direction
check
• Status
–
Assign diagnostic behavior
• In the
Operating mode
parameter, the
Switch
option is selected.
• In the
Switch output
function
parameter, the
Diagnostic behavior
option
is selected.
Select diagnostic behavior for
switch output.
• Alarm
• Alarm or warning
• Warning
–
Assign limit
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Limit
option is selected
in the
Switch output
function
parameter.
Select process variable for limit
function.
• Temperature
• Mass flow
• Corrected volume
flow
• FAD volume flow
• Volume flow
• Energy flow
• Heat flow
• Density
• Flow velocity
• 2nd temperature
delta heat
• Electronic
temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
–
Assign status
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Status
option is
selected in the
Switch
output function
parameter.
Select device status for switch
output.
• Off
• Low flow cut off
–
Switch-on value
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Limit
option is selected
in the
Switch output
function
parameter.
Enter measured value for the
switch-on point.
Signed floating-point
number
Depends on country
and nominal
diameter
Switch-off value
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Limit
option is selected
in the
Switch output
function
parameter.
Enter measured value for the
switch-off point.
Signed floating-point
number
–
Switch-on delay
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Limit
option is selected
in the
Switch output
function
parameter.
Define delay for the switch-on
of status output.
0.0 to 100.0 s
–
Содержание HART Proline t-mass I 300