System integration
Proline t-mass I 300 HART
74
Hauser
Assignment
Device variables
5
Temperature
6
Totalizer 1
7
Totalizer 2
8
Totalizer 3
8.3
Other settings
Burst mode functionality in accordance with HART 7 Specification:
Navigation
"Expert" menu → Communication → HART output → Burst configuration → Burst
configuration 1 to n
‣
Burst configuration
‣
Burst configuration 1 to n
Parameter overview with brief description
Parameter
Description
Selection / User entry
Burst mode 1 to n
Activate the HART burst mode for burst message X.
• Off
• On
Burst command 1 to n
Select the HART command that is sent to the HART master.
• Command 1
• Command 2
• Command 3
• Command 9
• Command 33
• Command 48
Burst variable 0
For HART command 9 and 33: select the HART device variable
or the process variable.
• Mass flow
• Corrected volume flow
• FAD volume flow
• Volume flow
• Temperature
• Density
• Flow velocity
• Pressure
• Energy flow
• Heat flow
• 2nd temperature delta heat
• Electronic temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Percent of range
• Measured current
• Current input 1
• Current input 2
• Current input 3
• Primary variable (PV)
• Secondary variable (SV)
• Tertiary variable (TV)
• Quaternary variable (QV)
• HART input
• Not used
Burst variable 1
For HART command 9 and 33: select the HART device variable
or the process variable.
See the
Burst variable 0
parameter.