Commissioning
Proline t-mass I 300 HART
84
Hauser
Duct height
Duct width
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User entry
Installation direction
–
Set sign of flow direction to match the
direction of the arrow on the sensor.
• Flow in arrow direction
• Flow against arrow
direction
Installation factor
–
Enter factor to compensate the
mounting-related measurement error.
0.01 to 100.0
Pipe shape
Only available with t-mass I.
Select the shape of the pipe.
• Circular
• Rectangular
Pipe inner diameter
Only available with t-mass I.
Enter the internal diameter of a circular
pipe.
0.050 to 5 m
Duct height
Only available with t-mass I.
Enter inner duct height. Duct height
and sensor shaft are parallel.
0.050 to 5 m
Duct width
Only available with t-mass I.
Enter inner duct width. The duct width
is vertical to the sensor shaft.
0.050 to 5 m
9.4.5
Configuring the status input
The
Status input
submenu guides the user systematically through all the parameters that
have to be set for configuring the status input.
Navigation
"Setup" menu → Status input
‣
Status input 1 to n
Assign status input
Terminal number
Active level
Terminal number
Response time status input
Terminal number