The OneCommand Utility User Manual
Page 44
•
Exceeded operational range - Critical: The adapter’s temperature is beyond normal
operational range. If the temperature continues to increase, the adapter shuts down. You
must determine the cause of the temperature problem and fix it immediately. Check for
system cooling issues. Common causes of system cooling issues include clogged air filters,
inoperable fans and air conditioning problems that cause high ambient air temperatures.
•
Exceeded operational range - Adapter stopped: The temperature has reached critical limit,
forcing the adapter to shut down. You must determine the cause of the temperature problem
and fix it before resuming operation. Check for system cooling issues. Common causes of
system cooling issues include clogged air filters, inoperable fans and air conditioning
problems that cause high ambient air temperatures.
After the system overheating issue is resolved and the adapter has cooled down, reboot the
system or, if the system supports hot swapping, cycle the power of the adapter slot.
Viewing iSCSI Adapter Information
When you select an iSCSI adapter from the discovery-tree, the Adapter Information tab contains general
attributes associated with the selected iSCSI adapter.
To view general iSCSI adapter information:
1.
Select Host view.
2.
Select an iSCSI adapter in the discovery-tree.
Figure 18: iSCSI Adapter Information tab
iSCSI Adapter Information Field Definitions
•
Model - The model of the selected adapter.
•
Serial Number - The serial number of the selected adapter.
•
Active Firmware Version - The version of the firmware running on the selected adapter.
Note: No iSCSI information is provided by the CIM provider on any version of VMware ESX.