396
Troubleshooting the Tape Library
Problem: The LCB detected an Ethernet connection failure with the FC I/O blade.
1
Note the ticket details, to determine FC I/O blade location and failure reason.
2
If a CAN and Ethernet connection failure is detected, ensure that the FC I/O blade is installed properly,
fully latched, secured, and powered on.
3
If the FC I/O blade has been removed from the library, select
Setup > FC I/O Blades > FC I/O Blade
Control > Remove
to exclude the FC I/O blade from library-initiated health check monitoring.
4
If only an Ethernet connectivity issue is reported, ensure that the Ethernet cable is properly connected
to both the appropriate port in the 9U Expansion Module that contains the FC I/O blade, and to one of
the 4 ports on the library control blade. Inspect the Ethernet cable for any damage, and disconnect and
reconnect as needed.
5
If the problem still persists, contact Service for further assistance.
6
You have three options:
a. Select
Close
to close the ticket now.
b. Select
Exit
to leave the ticket open for future troubleshooting.
c. Select
Back
to return to the Diagnostic Resolution.
DR064 - Resolve FC I/O Blade CAN Failure
This DR provides customer resolution steps for
T104
on page 305.
Problem: The LCB has lost its CAN connection with the FC I/O blade.
1
Check that the FC I/O blade is installed properly. It should not be loose, and it should be powered up.
2
Ensure that both module terminators are properly installed in the rear of the library.
3
Check the module terminators for any bent pins or other damage.
4
If the problem still persists, contact Service for further assistance.
5
You have three options:
a. Select
Close
to close the ticket now.
b. Select
Exit
to leave the ticket open for future troubleshooting.
c. Select
Back
to return to the Diagnostic Resolution.
DR065 - Resolve FC I/O Blade Temperature Alert
This DR provides customer resolution steps for
T105
on page 306.
Problem: A Fibre Channel I/O blade temperature exceeded the operating temperature limit.
1
Check the temperature of the room in which the library is installed. Ensure that it is below 32 ºC
(89.6 ºF).
2
Ensure that there are no open tickets indicating a problem with the FC I/O blade fan. If so, resolve that
ticket first, as a temperature alert can be caused by a faulty fan.
3
Otherwise, contact Service for further assistance in resolving the issue.
4
You have three options:
a. Select
Close
to close the ticket now.
b. Select
Exit
to leave the ticket open for future troubleshooting.
c. Select
Back
to return to the Diagnostic Resolution.
Содержание PowerVault ML6000
Страница 1: ...w w w d e l l c o m s u p p o r t d e l l c o m MaintenanceGuide Dell PowerVault ML6000 ...
Страница 14: ...xiv Tables ...
Страница 18: ...xviii Figures ...
Страница 452: ...434 Troubleshooting the Tape Library ...
Страница 456: ...438 Library Drawings Library Rear View Figure 32 ML6020 Rear View ...
Страница 463: ...PowerVault ML6000 Maintenance Guide 445 Figure 42 Model 1 Picker Assembly Figure 43 Model 2 Picker Assembly ...
Страница 466: ...448 Library Drawings Figure 46 Model 1 Parking Tab Parked Figure 47 Model 2 Parking Tab Parked ...
Страница 467: ...PowerVault ML6000 Maintenance Guide 449 Library Control Blade LCB Figure 48 Library Control Blade ...
Страница 468: ...450 Library Drawings Power Supplies Figure 49 Power Supplies ...
Страница 475: ...PowerVault ML6000 Maintenance Guide 457 Rack mounted Library Figure 56 Rack mounted Library Front ...
Страница 477: ...PowerVault ML6000 Maintenance Guide 459 Figure 58 Electrical System 5U Library Control Module ...
Страница 478: ...460 Library Drawings Figure 59 LCB Functions ...
Страница 479: ...PowerVault ML6000 Maintenance Guide 461 ...
Страница 480: ...462 Library Drawings Figure 60 Accessor Control Block Figure 61 Door and Import Export Board DIEB ...
Страница 481: ...PowerVault ML6000 Maintenance Guide 463 Figure 62 Door and Display Block Figure 63 Power System Block ...
Страница 482: ...464 Library Drawings Figure 64 Fan Control Board ...
Страница 483: ...PowerVault ML6000 Maintenance Guide 465 Figure 65 Library Cables ...
Страница 484: ...466 Library Drawings Figure 66 Library System Grounding ...
Страница 485: ...PowerVault ML6000 Maintenance Guide 467 Figure 67 Library Power System ...
Страница 486: ...468 Library Drawings ...
Страница 494: ...476 Glossary Y axis Y position The vertical position of the library s robotic arm ...