62-11039
3-3
3.3 STARTING UNIT -- ELECTRIC STANDBY OPERATION
WARNING
When performing service and/or maintenance procedures, make certain the unit is disconnected
from the power source and that the RS is in OFF position so that it is impossible for the unit to
start up automatically during the maintenance operation.
WARNING
Make sure the power plug is clean and dry before connecting to any electrical outlet/receptacle.
Do not connect to any electrical outlet without checking that it meets the 460/3/60 and 23 Amp
electrical requirements of the unit.
5. Place the START/RUN - OFF switch
in START/RUN position.
STANDBY
ENGINE
+36 F
-20
COMPARTMENT SWITCHES
3. Place the ENGINE/STANDBY
switch in STANDBY position
4. Place the desired compartment
switch(es) to on (1)
2. Connect standby cable to unit and then
turn the external power circuit breaker on.
1. Put all compartment switches in OFF (0)
position and place RS in OFF position
AND
turn
off the external power circuit breaker.
1
COMPARTMENT 1
COMPARTMENT 2
COMPARTMENT 3
0
0
0
1
1
1
6. The unit will then start automatically.