3-10
3.7 START--STOP OPERATION -- ENGINE/ROAD AND ELECTRIC STANDBY
COOL
DEFROST
ALARM
START-STOP
SETPOINT
BOX TEMPERATURE
ALARM LIST
SELECT
MANUAL
DEFROST
HEAT
CONTINUOUS
START/STOP MODE SELECTED
+36 F
-20
START--STOP/
CONTINUOUS
2
1. Press the START--STOP/CONTINUOUS key until
the START--STOP Light on the controller illumi-
nates.
2. Verify that “START/STOP MODE SELECTED” is displayed on the MessageCenter and that
the START-STOP light is illuminated. The unit is now in Start-Stop operation.
START--STOP
LIGHT
Automatic
Start--Stop
is
provided
to
permit
starting/stopping/restarting of the unit as required. This
feature allows full automatic control of the engine or
compressor starting and stopping by monitoring box
temperature, battery charging amps and engine coolant
temperature (Engine/Road only). The main function of
automatic cycling is to turn off the refrigeration system
near setpoint to provide a energy efficient temperature
control system and to initiate a restart sequence when
certain conditions are met. The Start--Stop/Continuous
key is pressed to select between Continuous Run and
Start--Stop operating modes. Refer to Section 4.2 for
more detailed information on Start--Stop Mode.
For compartment 1 only Start-Stop operation may be
tied to the setpoint ranges for frozen and perishable
loads. The START-STOP/CONTINUOUS key is locked
out if “START-STOP LOCKED” appears in the
MessageCenter when the key is pressed and the unit is
in Start--Stop Mode or “CONTINUOUS LOCKED”
appears in the MessageCenter when the key is pressed
and the unit is in Continuous Run Mode. Refer to the
configuration table Section 5.2.
If the engine fails to start after three start attempts, the
“FAILED TO START--AUTO MODE” alarm will be
activated. While running, if the unit shuts down on a
safety, or fails to run for the minimum run time, three
consecutive times, the
“FAILED TO RUN MINIMUM TIME” Alarm will be
activated. The shutdown counter is cleared when the
unit has run for 15 minutes, or when the engine cycles
off normally.
NOTE
In electric standby mode, the unit will stop for a
minimum of 5 minutes instead of 15 minutes.
Содержание VECTOR 1800 MT
Страница 1: ......
Страница 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Страница 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Страница 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Страница 21: ...1 7 62 11039 ...
Страница 303: ...10 1 62 11039 ...
Страница 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Страница 311: ...10 9 62 11039 FROM PREVIOUS SHT ...