62-11039
5-8
CONFIGURATION
SELECTIONS
DESCRIPTION
•
ECONO MAX. TEMP
--19
°
F to +119
°
F
(--28.3
°
C to
+48.3
°
C )
in 0.5
°
F or
°
C
increments
Default:
119
°
F
(48.3
°
C )
OFF
Select the upper limit of the ambient range desired
for this parameter. See Section 4.6 for more infor-
mation on Econo Max. Temp.
•
ECONO DELTA--T
OFF
+3.6
°
F to +27.0
°
F
(+2
°
C to 15
°
C)
in 0.5
°
C or
°
F in-
crements
Select the desired Delta--T value for activation of
ProductShield Econo: Go To S/S
This parameter is not available for Econo: Go To
Continuous Run
•
PRODUCTSHIELD HIGH AIR
OFF
ON
OFF = The unit will operate normally in high and
low speeds.
ON = The unit will operate in high speed when the
ambient air temperature falls OUTSIDE the mini-
mum / maximum temperature range (selected set-
tings for HIGH AIR MIN TEMP, HIGH AIR MAX
TEMP, AND HIGH AIR DELTA--T -- see below)
•
HIGH AIR MIN. TEMP
--19
°
F to +119
°
F
(--28.3
°
C to
+48.3
°
C )
in 0.5
°
F or
°
C
increments
Default:
119
°
F
(48.3
°
C )
OFF
Select the lower limit of the ambient range desired
for this parameter. See Section 4.6 for more infor-
mation on High Air Min. Temp.
•
HIGH AIR MAX. TEMP
--19
°
F to +119
°
F
(--28.3
°
C to
+48.3
°
C )
in 0.5
°
F or
°
C
increments
Default:
119
°
F
(48.3
°
C )
OFF
Select the upper limit of the ambient range desired
for this parameter. See Section 4.6 for more infor-
mation on Econo Max. Temp.
•
HIGH AIR DELTA--T
OFF
+3.6
°
F to +27.0
°
F
(+2
°
C to 15
°
C)
in 0.5
°
C or
°
F in-
crements
Select the desired Delta--T value for activation of
ProductShield High Air
PRODUCTSHIELD WINTER
OFF
--20
°
F to +32.0
°
F
(--28.9
°
C to 0
°
C)
in 0.5
°
C or
°
F in-
crements
Select the desired ambient temperature for activa-
tion of installed ProductShield Winter. When ambi-
ent temperature falls below this selected value, the
unit will run in Continuous Run only. See Section
4.6 for more information on ProductShield Winter.
RANGE (1--2) LOCK
COMPARTMENT 1 ONLY
OFF
START--STOP
CONTINUOUS
OFF = If both Range 1 & Range 2 Locks are off,
Start--Stop or Continuous Run may be selected.
If either Range 1 or Range 2 is not OFF, the unit
will operate in the selected mode whenever the set-
point is within that range.
START--STOP = The unit will always operate in
Start--Stop whenever the setpoint is between the
minimum & maximum temperatures for that range
(see below).
CONTINUOUS = The unit will always operate in
Continuous Run whenever the setpoint is between
the minimum & maximum temperatures for that
range (see below).
Содержание VECTOR 1800 MT
Страница 1: ......
Страница 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Страница 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Страница 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Страница 21: ...1 7 62 11039 ...
Страница 303: ...10 1 62 11039 ...
Страница 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Страница 311: ...10 9 62 11039 FROM PREVIOUS SHT ...