62-11039
7-79
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
161 CHECK SUCTION TEMP SENSOR (CST)
•
TRIGGER–ON: Suction Temp Sensor (CST) is not within the maximum range of --53
°
F to +158
°
F
(--47
°
C to +70
°
C)
•
UNIT CONTROL: Engine and standby operation: pre trip will fail and display “PRE TRIP FAIL AND
•
UNIT CONTROL: Engine and standby operation: pre--trip will fail and display “PRE--TRIP FAIL AND
COMPLETED”.
•
RESET CONDITION: Auto Reset when suction temperature sensor is in range or, alarm may be
manually reset via keypad or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active alarm
should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
1.
Check Suction Temp Sensor
a. Inspect Suction Temp Sensor &
connector
No damage to sensor
No damage, moisture, or corrosion in connector
b. Check
Suction
Temp
Sensor
resistance (See Note 4)
(Refer to Section 8.28 for complete resistance chart)
10,000 Ohms @ 77
°
F (25
°
C)
2.
Check Suction Temp Sensor Wiring
a. Inspect harness & control box
connector pins & terminals (See
wiring schematic)
No physical damage to harness.
No damaged or corroded pins
3.
Check Suction Temp Sensor Connector
a.Locate and inspect remote sensor
connector
Cap is in place.
No physical damage.
No moisture or corrosion.
Содержание VECTOR 1800 MT
Страница 1: ......
Страница 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Страница 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Страница 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Страница 21: ...1 7 62 11039 ...
Страница 303: ...10 1 62 11039 ...
Страница 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Страница 311: ...10 9 62 11039 FROM PREVIOUS SHT ...