62-11039
5-5
CONFIGURATION
SELECTIONS
DESCRIPTION
FUEL TANK SIZE
OFF
30 GALLONS
50 GALLONS
75 GALLONS
100 GALLONS
120 GALLONS
OFF = No Low Fuel Level
Switch
or
0 to 100%
Sensor
is installed in the tank; OR
A Low Fuel Level
Switch
or a
0 to 100% Sensor
is
installed in the tank, but the unit will not shutdown
due to a Low Fuel Level Alarm.
30 -- 120 GALLONS = When a Low Fuel Level
Switch
is installed, and the LOW FUEL
LEVEL WARNING (alarm 1) is on, the unit
will shutdown (alarm 19) after a time delay
(Refer to chart below)
30 gal
30 min
50 gal
60 min
75 gal
90 min
100 gal
120 min
120 gal
150 min
OR
If a
0 to 100% Sensor
is installed, the low fuel level
WARNING (alarm 1) will come on when the level
reaches 15% or less, and the unit will shutdown
(alarm 19) when the level reaches 10%.
DIESEL MAX GEN CURR
26A
10 TO 35
in 0.5A increments
Use factory default settings only.
DO NOT OPERATE UNIT WITH DIFFERENT SET-
TINGS.
STANDBY MAX GEN CURR
22A
10 TO 35
in 0.5A increments
Use factory default settings only.
DO NOT OPERATE UNIT WITH DIFFERENT SET-
TINGS.
INITIAL GENERATOR CURR
17A
10 TO 35
in 0.5A increments
Use factory default settings only.
DO NOT OPERATE UNIT WITH DIFFERENT SET-
TINGS.
DIESEL OFFSET FOR CURR
4A
10 TO 10
in 0.5A increments
Use factory default settings only.
DO NOT OPERATE UNIT WITH DIFFERENT SET-
TINGS.
STANDBY STARTUP DELAY
OFF
5
10
15
20 SECONDS
Used in starting the system in standby from power
up. This helps to prevent multiple units on the same
power drop from restarting at the same time.
DISPLAY TOTAL ENGINE HR
NO /
YES
YES = This hourmeter will be displayed during the
startup messaging sequence and will be in hour-
meter menu.
NO = This hourmeter will not be displayed during
the startup messaging sequence and will be shown
with the “other meters and counters”.
DISPLAY STANDBY RUN HR
NO /
YES
YES = This hourmeter will be displayed during the
startup messaging sequence and will be in hour-
meter menu.
NO = This hourmeter will not be displayed during
the startup messaging sequence and will be shown
with the “other meters and counters”.
Содержание VECTOR 1800 MT
Страница 1: ......
Страница 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Страница 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Страница 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Страница 21: ...1 7 62 11039 ...
Страница 303: ...10 1 62 11039 ...
Страница 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Страница 311: ...10 9 62 11039 FROM PREVIOUS SHT ...