62-11039
7-35
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
59
DATALOGGER NOT RECORDING
•
TRIGGER–ON: No data is being recorded by the data recorder.
TRIGGER ON: No data is being recorded by the data recorder.
•
UNIT CONTROL: Engine and standby operation: alarm only.
•
RESET CONDITION: Alarm may be manually reset via keypad.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1) Operate the unit through the appropriate modes to see if any active alarm occurs. Continue
with the steps below as necessary.
1.
Clear Alarm
a. Clear Active Alarm(s)
Alarms Clear
b. Check for Active Alarm reoccurrence If Inactive, download all data & retain.
If Active, go to next step
2.
Microprocessor Defective
a. Download previous data using
Download PC Card, or DataManager
Program.
Data retrieval OK
b. Replace microprocessor & set
Configurations, Functional
Parameters, Enter hours from
removed microprocessor, set
Maintenance Hour Meters, and Data
Recorder Setup.
New microprocessor in place
NOTE: Specific configurations or IntelliSet settings may be found on the TransCentral Website (Authorized Carrier
Transicold Dealers only.)
60
DATALOGGER TIME WRONG
•
TRIGGER–ON: The real time clock in the Data Recorder does not contain a valid date.
•
UNIT CONTROL: Engine and standby operation: alarm only
•
UNIT CONTROL: Engine and standby operation: alarm only.
•
RESET CONDITION: Auto Reset when the Data Recorder Real Time Clock is reset, or alarm may be
manually reset by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active alarm
should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
1.
Check Real Time Cloc
k
a. Check Real Time Clock in the Data List,
or using DataManager or Service
Manager.
Must show correct date and time. Change as needed
(Configuration List).
2.
Reset Microprocessor
a. Turn main switch off for 30 seconds,
then turn on.
Microprocessor powers up OK
b. Check for valid Real Time Clock
reading in Data List
Valid date and time in memory.
Alarm is cleared automatically
c. Real Time Clock can not be
changed.
Replace microprocessor
3.
Microprocessor Defective
a. Download previous data using
Download PC Card, or DataManager
Program.
Data retrieval OK
b. Replace microprocessor & set
Configurations, Functional
Parameters, Enter hours from
removed microprocessor, set
Maintenance Hour Meters, and Data
Recorder Setup.
New microprocessor in place
Содержание VECTOR 1800 MT
Страница 1: ......
Страница 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Страница 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Страница 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Страница 21: ...1 7 62 11039 ...
Страница 303: ...10 1 62 11039 ...
Страница 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Страница 311: ...10 9 62 11039 FROM PREVIOUS SHT ...